INSTALLATION MANUAL
Multi-Zone Heat Pump Systems
1.5 to 5 Tons
Dual and Tri-Zone
Multi F
Quad-Zone
Multi F
Eight-Zone
Multi F MAX

Table of Contents

Other manuals for LG MULTI F

Questions and Answers:

LG MULTI F Specifications

General IconGeneral
Inverter TechnologyYes
Power Supply220-240V, 50Hz
TypeMulti Split
RefrigerantR410A
Energy Efficiency Class (Cooling)A++ to A+++ (depending on the model)
Energy Efficiency Class (Heating)A++
Indoor Unit CompatibilityMultiple (Ceiling Cassette, Wall Mount, etc.)
Operating Temperature Range (Heating)-15°C to 24°C
ControlRemote Control, Wi-Fi
Seasonal Energy Efficiency Ratio (SEER)Up to 8.5 (depending on the model)
Compressor TypeInverter Compressor
Operating Temperature (Cooling)5°C to 43°C
Operating Temperature (Heating)-15°C to 24°C
Noise Level (Indoor)19-45 dB(A) (depending on the model and indoor unit type)
Dimensions (Indoor Unit)Varies by model
Dimensions (Outdoor Unit)Varies by model
Weight (Indoor Unit)Varies by model
Weight (Outdoor Unit)Varies by model
FeaturesSmart Diagnosis

Summary

Safety Instructions

Table of Symbols

Defines symbols used for safety warnings, indicating hazards and actions to avoid.

Installation Safety

Covers general safety warnings for installing the unit, including electrical hazards and proper handling.

Wiring Safety

Provides critical safety instructions for electrical wiring, connections, and grounding.

Operation Safety

Outlines safety precautions related to operating the unit, including avoiding water and handling moving parts.

Nomenclature

Multi-Zone Systems - Indoor Units and Outdoor Units

Explains the coding system for identifying Multi-Zone indoor and outdoor units.

Branch Distribution Units

Details the nomenclature for Branch Distribution Units, including type and port connections.

General Data

Multi F Outdoor Unit Specifications

Provides detailed specifications for Multi F outdoor units, including capacity, operating range, and dimensions.

Multi F Outdoor Unit Electrical Data

Lists electrical specifications for Multi F outdoor units, including voltage, MCA, and MOP.

Multi F MAX Outdoor Unit General Data

Presents general data for Multi F MAX outdoor units, covering capacities and electrical requirements.

Multi F MAX Electrical Data

Details electrical specifications for Multi F MAX outdoor units, including fan and motor data.

Branch Distribution Unit General Data

Provides general data for Branch Distribution Units, including capacity and piping connections.

Installation

Transporting Lifting the Outdoor Unit

Instructions for safely transporting and lifting the outdoor unit, emphasizing weight and rigging.

Selecting the Best Location for the Outdoor Unit

Guidelines for choosing an optimal location for the outdoor unit, considering airflow and safety.

Rooftop Installations

Specific considerations for installing outdoor units on rooftops, including leveling and anchoring.

Oceanside Installation Precautions

Precautions for installing units in corrosive seaside environments, including windbreakers.

Tie-Downs and Lightning Protection

Instructions for securing units against wind/earthquakes and protecting them from lightning.

Outdoor Unit Service Access and Allowable Clearances

Specifies required clearances around the outdoor unit for airflow and service access.

Installing Outdoor Units Indoors

Guidance on installing outdoor units in indoor spaces, outlining benefits and design considerations.

Louver Recommendations for Outdoor Unit Enclosure

Recommendations for selecting and designing louvers for outdoor unit enclosures to ensure proper airflow.

Mounting Anchoring the Outdoor Units

Mounting Anchoring the Outdoor Unit General Specifications

General specifications and procedures for securely mounting and anchoring outdoor units.

Outdoor Unit Platform Concrete Specifications

Details on the concrete foundation requirements for outdoor unit mounting.

Anchoring the Outdoor Unit

Instructions on how to properly anchor the outdoor unit to its mounting platform.

General Refrigerant Piping System Information

LG Air Conditioner Technical Solution (LATS) Software

Information on LG's LATS software for designing and validating refrigerant piping systems.

Refrigerant Safety Standards

Guidelines for refrigerant safety and maximum allowable concentrations in occupied spaces.

Device Connection Limitations

Specifies limitations on the number and capacity of indoor units that can be connected.

Multi F Outdoor Unit Piping Length and Elevation Limitations

Details the maximum allowable piping lengths and elevation differences for Multi F systems.

Multi F MAX Outdoor Unit Piping Length and Elevation Limitations

Specifies piping length and elevation limits for Multi F MAX systems with branch distribution units.

Using Refrigerant Components

Guidance on using field-supplied elbows, Y-branches, and branch distribution units.

Selecting Field-Supplied Copper Tubing

Information on selecting and using appropriate ACR copper tubing for LG Multi F systems.

Copper Expansion and Contraction

General Example

An example calculation for linear pipe expansion based on temperature change.

Vapor Line

Details on calculating anticipated linear expansion for vapor lines.

Liquid Line

Information on the minimal change in length for liquid lines due to temperature.

Piping Handling

Keep Pipes Capped While Storing

Instructions for storing refrigerant pipes properly to prevent contamination.

Refrigerant System Engineering

No Pipe Size Substitutions

Emphasizes using only specified pipe sizes to prevent system malfunction.

No In-line Refrigeration Components

Prohibits after-market accessories like oil traps or solenoid valves in the refrigerant piping.

Field-Provided Isolation Ball Valves

Discusses considerations for installing isolation valves, including pressure drops.

Using Elbows

Guidance on using field-supplied long radius elbows and accounting for pressure loss.

Pipe Bends

Recommendations for using long radius bends when bending soft copper.

Obstacles

Pipe Supports

Instructions for properly supporting refrigerant pipes to prevent sagging and oil traps.

Flaring and Brazing Procedures

Flaring Procedure

Step-by-step guide for performing correct flare connections for refrigerant piping.

Flared Connection Dimensions Tightening Torque

Provides dimensions and torque specifications for flared connections.

Brazing Procedure

Instructions for performing brazing procedures, emphasizing safety and material compatibility.

Installing Multi F Systems

Multi F Outdoor Unit to Indoor Unit Piping Connections

Details on connecting piping between Multi F outdoor and indoor units.

Installing Field Piping to the Outdoor Unit Piping Connections

Procedure for connecting field-supplied piping to the outdoor unit service ports.

Tightening the Flare Nuts

Instructions for properly tightening flare nuts using torque specifications.

Using the Connection Socket

Guidance on installing connection sockets for indoor units when piping.

Installing Multi F MAX Systems

Multi F MAX Refrigerant Piping Connections Piping Routes

Describes the four possible piping installation directions for Multi F MAX outdoor units.

Multi F MAX Outdoor Unit System Piping Connections

Provides connection types and tables for Multi F MAX outdoor units.

Branch Distribution to Indoor Unit Piping Connections

Instructions for connecting refrigerant pipes from branch distribution units to indoor units.

Bundling and Special Applications

Bundling

Instructions for bundling refrigerant pipes, drain hose, and cables with vinyl tape.

Special Applications

Guidance for specific installation scenarios like outdoor units below or above indoor units.

Condensate Drain Piping

Condensate Drain Piping

Requirements for condensate drain piping construction and material.

Drain Leak Test

Procedure for performing a leak test on the drainage system 24 hours after installation.

Insulation

General Piping System Insulation

Guidelines for correctly insulating all refrigerant piping, Y-branches, and valves.

Minimum Refrigerant Pipe Ethylene Propylene Diene Methylene (EPDM) Insulation Wall Thickness Requirements

Table detailing minimum EPDM insulation wall thickness based on location and pipe classification.

Installing the Insulation

Instructions for applying insulation material to refrigerant piping and ensuring proper fit.

Insulating Piping Joints

Steps for insulating joints and connections to prevent air gaps and ensure proper fit.

Y-Branch Kit Insulation

Guidance on applying the included insulation jackets for Y-branch fittings.

Electrical

General Information

General guidelines for electrical wiring, emphasizing safety and compliance with codes.

Location Accessing the Power Wiring and Communications Cable Connections

Instructions for accessing the outdoor unit for power and communications cable connections.

Power Wiring Communication Cable Specifications

Details on specifications for power and communication cables, including gauge and insulation.

Outdoor Unit Wiring Connection Guidelines

Best practices for terminating power wiring at the power terminal block.

Test Run

Before the Test Run

Checks to perform before starting the test run, ensuring proper connections and valve positions.

Installing the Remote Controller Batteries

Instructions for inserting batteries into the remote controller for operation.

Test Run Procedure

Steps for operating the system and evaluating its performance during a test run.

DIP Switch Settings for Optional Modes

Outdoor Unit DIP Switch Settings

Explains how to set DIP switches for various optional modes and functions.

Forced Cooling Operation Function

Procedure for enabling forced cooling operation, typically for adding refrigerant in winter.

Wiring Error Check

Procedure to verify proper wiring installation using LEDs on the outdoor unit PCB.

Reducing Power Consumption

Enables efficient operation by lowering maximum power consumption, reducing MCA.

Reducing Power Consumption with Mode Lock

Combines power saving with mode lock for applications requiring a specific mode.

Night Quiet Mode

Lowers operation sound by adjusting compressor frequency and fan speeds.

Night Quiet Mode with Mode Lock

Combines Night Quiet Mode with Mode Lock to reduce sound and fix operation mode.

Mode Lock

Prevents mixed mode operation by locking the system into cooling or heating.

PCB Display (1824 k Model Only)

Instructions for checking cycle data using the TACT-SW1 on the PCB.

Error Codes

Troubleshooting Using Error Codes

Guidance on interpreting and troubleshooting error codes displayed on units and software.

Decoding the Error Display

Explains how to read error codes from indoor unit LEDs based on blink patterns.

Error Code Nomenclature Definitions

Defines terms like MICOM and EPROM used in error code reporting.

Indoor Unit Error Codes

A table listing common error codes for indoor units and their operation status.

Outdoor Unit Error Codes

A table listing common error codes for outdoor units and their LED blink patterns.

LG Monitoring View (LGMV) Diagnostic Software

LGMV Display

Details the real-time data displayed by LGMV software, including compressor and fan speeds.

Additional screens can be accessed by tabs on the main screen

Describes additional screens available in LGMV, including Cycleview, Graph, Control FTN, and Useful Tab.

LG SMART INVERTER MONITORING SYSTEM (SIMS)

LG SIMs

Overview of SIMS capability for monitoring and troubleshooting LG Duct Free Systems.

SIMs App Main Info Screen

Description of the main screen and how to access current readings and operational info.

SIMs App Screens

Details on various SIMs app screens like Outdoor Info, Indoor Info, and Graph Info.

Maintenance Recommendations

Installation Checklist

Major Component Rough-In

Checklist items for the initial installation of major components.

Piping and Insulation

Checklist items for piping material, installation, and insulation.

Brazing Practices

Checklist items for proper brazing techniques and materials.

Refrigerant Piping Design and System

Checklist items related to refrigerant piping design, material handling, and installation.

Condensate Pump Drain Installation

Checklist items for correct installation and connection of condensate drain systems.

Power Wire and Communications Cables

Checklist items for proper installation of power wiring and communication cables.

Multi F Refrigerant Charge Worksheet

Multi F Outdoor Unit Factory Charge

Table showing factory refrigerant charge for Multi F outdoor units.

Multi F Outdoor Unit Additional Refrigerant Charge Formula

Formula to calculate additional refrigerant needed based on piping length.

Multi F Outdoor Unit Piping Specifications

Specifications for Multi F outdoor unit piping, including lengths and additional charge.

Multi F Refrigerant Charge Calculations

Worksheet to calculate the total additional refrigerant charge required for the system.

Multi F MAX Refrigerant Charge Worksheet

Multi F MAX Outdoor Unit Factory Charge

Table showing factory refrigerant charge for Multi F MAX outdoor units.

Multi F MAX Outdoor Unit Piping Specifications

Specifications for Multi F MAX outdoor unit piping, including lengths and additional charge.

Multi F MAX Refrigerant Charge Calculations

Worksheet to calculate the total additional refrigerant charge required for Multi F MAX systems.

Safety Instructions

Table of Symbols

Defines symbols used for safety warnings, indicating hazards and actions to avoid.

Installation Safety

Covers general safety warnings for installing the unit, including electrical hazards and proper handling.

Wiring Safety

Provides critical safety instructions for electrical wiring, connections, and grounding.

Operation Safety

Outlines safety precautions related to operating the unit, including avoiding water and handling moving parts.

Specifications

Multi F Outdoor Unit Specifications

Provides detailed specifications for Multi F outdoor units, including capacity, operating range, and dimensions.

Multi F MAX Outdoor Unit General Data

Presents general data for Multi F MAX outdoor units, covering capacities and electrical requirements.

Multi F MAX Branch Distribution Units

Provides general data for Multi F MAX Branch Distribution Units, including capacity and piping.

Multi F Multi Zone Ceiling Cassette Indoor Unit Specifications

Details specifications for Multi F Multi Zone Ceiling Cassette Indoor Units, including capacity and dimensions.

ELECTRICAL DATA

Multi F Outdoor Unit Electrical Data

Lists electrical specifications for Multi F outdoor units, including voltage, MCA, and MOP.

Multi F MAX Electrical Data

Details electrical specifications for Multi F MAX outdoor units, including fan and motor data.

R410 A REFRIGERANT

GENERAL INSTALLATION GUIDELINES

Location for Outdoor Unit

Guidelines for selecting an optimal location for the outdoor unit, considering hazards and conditions.

Oceanside Installation Precautions

Precautions for installing units in corrosive seaside environments, including windbreakers.

Rooftop Installations

Specific considerations for installing outdoor units on rooftops, including leveling and anchoring.

Planning for Snow and Ice

Measures for operating the unit in snowy or cold conditions, including raised platforms.

Tie-Downs and Lightning Protection

Instructions for securing units against wind/earthquakes and protecting them from lightning.

Service Access and Allowable Clearances for Outdoor Unit

Specifies required clearances around the outdoor unit for airflow and service access.

Allowable Clearances for Outdoor Unit

Provides diagrams and measurements for required clearances with various obstacles.

Rigging Instructions Platform Instructions for Outdoor Unit

Guidance on safely rigging and lifting outdoor units and preparing mounting platforms.

Concrete Platform Specifications

Details on the concrete foundation requirements for outdoor unit mounting.

Anchoring the Outdoor Unit

Instructions on how to properly anchor the outdoor unit to its mounting platform.

Outdoor Unit Foundation Requirements.

Specifies requirements for outdoor unit foundations, including bolt type and depth.

Bolting the Outdoor Unit to the Platform

Instructions for securely bolting the outdoor unit to its platform, including H-beam support.

Location for Multi F MAX Branch Distribution Units

Guidance for selecting the best indoor location for Multi F MAX branch distribution units.

Branch Distribution Unit Orientation

Details acceptable orientations for installing branch distribution units for proper valve seating.

Wall Mount Installation - Hangers Only

Instructions for mounting branch distribution units to a wall using hangers.

Piping Preparation

Steps for preparing refrigerant piping, including cutting, deburring, and flaring.

Creating a Flare Fitting

Step-by-step guide for performing correct flare connections for refrigerant piping.

Outdoor Unit Pipe Connections

Instructions for connecting pipes to the outdoor unit, emphasizing brazing and leak testing.

Refrigerant Piping

Guidance on insulating drain piping and general refrigerant piping.

Obstacles

How to route refrigerant piping around obstacles like beams or concrete structures.

Pipe Slope

Specifies the allowable slope for horizontal refrigerant piping.

In-line Refrigeration Components

Prohibits after-market accessories like oil traps or solenoid valves in the refrigerant piping.

No Pipe Size Substitutions

Emphasizes using only specified pipe sizes to prevent system malfunction.

Copper Expansion and Contraction

Explains how to calculate and accommodate pipe expansion due to temperature changes.

PIPING CONNECTIONS

Multi F Outdoor Unit Piping Length and Elevation Limitations

Details the maximum allowable piping lengths and elevation differences for Multi F systems.

Device Connection Limitations

Specifies limitations on the number and capacity of indoor units that can be connected.

Using Refrigerant Components

Guidance on using field-supplied elbows, Y-branches, and branch distribution units.

Multi F MAX Outdoor Unit Piping Length and Elevation Limitations

Specifies piping length and elevation limits for Multi F MAX systems with branch distribution units.

Multi F MAX System Example with One Branch Distribution Unit

Example illustrating piping for a Multi F MAX system with one branch distribution unit.

Multi F MAX System Example with Two Branch Distribution Units

Example illustrating piping for a Multi F MAX system with two branch distribution units.

Multi F Outdoor Unit to Indoor Unit Piping Connections

Details on connecting piping between Multi F outdoor and indoor units.

Using the Connection Socket

Guidance on installing connection sockets for indoor units when piping.

Multi F MAX Outdoor Unit System Piping Connections

Provides connection types and tables for Multi F MAX outdoor units.

Branch Distribution to Indoor Unit Piping Connections

Instructions for connecting refrigerant pipes from branch distribution units to indoor units.

Outdoor Unit Condensate Drain Piping

Requirements for condensate drain piping construction and material.

REFRIGERANT PIPING PREPARATION

Flushing the Refrigerant Piping

Method for cleaning refrigerant piping using pressurized nitrogen gas.

Leak Test and Vacuum Procedures

Steps for checking leaks and evacuating the system to remove non-condensibles.

Before the Leak Test

Checks to perform before starting the leak test, ensuring proper connections.

Pressure Gauge Hookup

Instructions for connecting the manifold valve and nitrogen gas cylinder for leak testing.

Leak Test Procedure

Procedure for pressurizing the system with nitrogen and testing for leaks.

Essential Points for Leak Testing

Key adherence points for successful leak testing, including pressure levels and time.

Vacuum Procedure

Steps for performing vacuum drying on the refrigerant piping and indoor units.

Refrigerant Charge

Determining and adding the correct refrigerant charge based on piping length and formulas.

Refrigerant Piping System Insulation

Guidelines for correctly insulating all refrigerant piping, Y-branches, and valves.

Pipe Sleeves at Penetrations

Requirements for pipe sleeves used at wall, floor, and underground penetrations.

Underground Refrigerant Piping

Instructions for routing underground refrigerant piping within protective sleeves.

Installing the Insulation

Instructions for applying insulation material to refrigerant piping and ensuring proper fit.

Insulating Piping Joints

Steps for insulating joints and connections to prevent air gaps and ensure proper fit.

Bundling

Instructions for bundling refrigerant pipes, drain hose, and cables with vinyl tape.

Special Applications

Guidance for specific installation scenarios like outdoor units below or above indoor units.

Y-Branch Kit Insulation

Guidance on applying the included insulation jackets for Y-branch fittings.

WIRING

General Information

General guidelines for electrical wiring, emphasizing safety and compliance with codes.

Power Supply Power Wiring Specifications

Details on power supply requirements and specifications for wiring.

General Communication Cable Specifications

Specifications for communication cables, including gauge and insulation requirements.

Outdoor Unit Wiring Connection Guidelines

Best practices for terminating power wiring at the power terminal block.

Connecting the Power Wiring Communications Cable to the Outdoor Unit

Instructions for connecting power and communication cables to the outdoor unit.

Connecting the Power Wiring Communications Cable to the Branch Distribution Unit (Multi F MAX Systems Only)

Procedure for connecting cables between outdoor/BD units and indoor units for Multi F MAX.

PI485

From Indoor Units to Remote Controllers

Between Multiple Indoor Units Operating as a Group (Group Control)

Instructions for setting up multiple indoor units for group control, defining Master and Slave units.

Troubleshooting

LG Monitoring View (LGMV) Diagnostic Software

Information on using LGMV software for system monitoring and troubleshooting.

Error Codes

Guides for interpreting error codes displayed on indoor and outdoor units.

Installation Checklist

Major Component Rough-In

Checklist items for the initial installation of major components.

Piping and Insulation

Checklist items for piping material, installation, and insulation.

Brazing Practices

Checklist items for proper brazing techniques and materials.

Refrigerant Piping

Checklist items related to refrigerant piping design, material handling, and installation.

Condensate Pump Drain Installation

Checklist items for correct installation and connection of condensate drain systems.

Power Wire and Communications Cables

Checklist items for proper installation of power wiring and communication cables.

Multi F Refrigerant Charge Worksheet

Multi F Outdoor Unit Factory Charge

Table showing factory refrigerant charge for Multi F outdoor units.

Multi F Outdoor Unit Additional Refrigerant Charge Formula

Formula to calculate additional refrigerant needed based on piping length.

Multi F Outdoor Unit Piping Specifications

Specifications for Multi F outdoor unit piping, including lengths and additional charge.

Multi F Refrigerant Charge Calculations

Worksheet to calculate the total additional refrigerant charge required for the system.

Multi F MAX Refrigerant Charge Worksheet

Multi F MAX Outdoor Unit Factory Charge

Table showing factory refrigerant charge for Multi F MAX outdoor units.

Multi F MAX Outdoor Unit Piping Specifications

Specifications for Multi F MAX outdoor unit piping, including lengths and additional charge.

Multi F MAX Refrigerant Charge Calculations

Worksheet to calculate the total additional refrigerant charge required for Multi F MAX systems.

Safety Precautions

Installation Safety

General safety guidelines for installation, covering grounding and electrical precautions.

Operation Safety

Safety precautions related to operating the unit, including avoiding water and sharp edges.

Installation of Indoor, Outdoor Unit

Select the best location

Guidelines for choosing the best location for indoor units, considering airflow and drainage.

Seaside Applications and Installation

Precautions for installing units in corrosive seaside environments, including windbreakers.

Seasonal Wind And Cautions In Winter

Measures for operating the unit in snowy or cold conditions, including raised platforms.

Piping length and elevation

Details on maximum allowable piping lengths and elevation differences for Multi Piping systems.

Connecting the piping

# Standard Artcool Mirror Type

Instructions for connecting piping and drain hose for Standard/Artcool Mirror type indoor units.

# Standard Libero Artcool Libero Type

Instructions for connecting piping for Standard/Artcool Libero type indoor units.

HEAT INSULATION

Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance [over 120 C(248 F)].

Guidance on using heat insulation material for refrigerant piping with excellent heat resistance.

Precautions in high humidity circum stance:

Measures to take in high humidity environments to prevent water drops and ensure proper operation.

Drain Piping

[Standard Standard Libero Artcool Mirror Type]

Instructions for drain piping slope and connection for Standard/Libero/Artcool Mirror types.

How To Fix

Installation of filters

Instructions for detaching tapes from the plasma filter.

Installation plate

Steps for mounting the installation plate on the wall, ensuring proper alignment.

Wiring Connection

Connecting cable

Instructions for connecting the cable to the indoor unit control board.

Conduit connection

Installation of Wired Remote Controller(Optional)

Reclamation to the surface of the wall

Steps for mounting the remote controller setup board on the wall.

Upper part guide groove

Instructions on setting up the remote controller cable in the upper direction.

Right part guide groove

Instructions on setting up the remote controller cable in the right direction.

Installation of Decorative Panel

HEAT INSULATION

Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance [over 120 C(248 F)].

Guidance on using heat insulation material for refrigerant piping with excellent heat resistance.

Precautions in high humidity circum stance:

Measures to take in high humidity environments to prevent water drops and ensure proper operation.

Drain Piping

[Standard Standard Libero Artcool Mirror Type]

Instructions for drain piping slope and connection for Standard/Libero/Artcool Mirror types.

Flaring Work and Connection of Piping

Flaring work

Main cause of gas leakage is defect in flaring work. Carry out correct flaring work.

Burrs removal

Instructions for completely removing all burrs from pipe ends after cutting.

Putting nut on

Instructions for placing flare nuts on the pipe/tube after completing burr removal.

Flaring work

Instructions for carrying out flaring work using a flaring tool.

Check

Procedure for inspecting the flared pipe end for defects.

Connection of piping - Outdoor

Steps for connecting piping to the outdoor unit, including tightening flare nuts.

Branch

Y branch

Ensures branch pipes are attached horizontally or vertically, with correct orientation.

Installation

Installation of The Main Unit

Instructions for installing the main unit, covering ceiling-suspended and wall-mounted types.

Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit

Connect the cable to the Indoor unit.

Instructions for connecting wires to the indoor unit control board, matching colors and terminals.

Connect the cable to the Distributor unit.

Procedure for connecting cables to the branch distribution unit for Multi F MAX systems.

Connect the cable to the Outdoor unit.

Instructions for connecting power and communication cables to the outdoor unit control board.

How to connect wiring to the terminals

Detailed steps on connecting wires to terminals, including strand wiring and tightening.

Checking the Drainage, Insulating the Pipe and Special Piping Applications

Checking the drainage

Procedure to check drainage by spraying water and verifying for leaks.

Insulating the Pipe and Special Piping Applications

Instructions for insulating piping and drain hoses, including securing and sealing.

Air Purging and Evacuation

Leak Checking

Procedure for performing a leak test using nitrogen gas and soap solution.

Evacuation

Steps for vacuum drying the system to remove non-condensibles and moisture.

Charging

Important:

Note on when additional refrigerant charging is necessary based on total piping length.

Multiple Piping Models

Provides calculations for additional refrigerant charge based on piping length for multiple indoor units.

Installation PI485

Test Running

Prepare remote control

Instructions for inserting batteries into the remote controller.

Evaluation of the performance

Steps to evaluate system performance, check refrigerant charge, and temperatures.

Function

Dip SW Setting

Explains DIP switch settings for various functions and modes.

Forced Cooling Operation

Procedure for enabling forced cooling operation, typically for adding refrigerant in winter.

Wiring Error Check

Procedure to verify proper wiring installation using LEDs on the outdoor unit PCB.

Saving Power Consumption

Enables efficient operation by lowering maximum power consumption, reducing MCA.

Reducing Power Consumption with Mode Lock

Combines power saving with mode lock for applications requiring a specific mode.

Night Quiet Mode

Lowers operation sound by adjusting compressor frequency and fan speeds.

Night Quiet Mode with Mode Lock

Combines Night Quiet Mode with Mode Lock to reduce sound and fix operation mode.

Mode Lock

Prevents mixed mode operation by locking the system into cooling or heating.