EasyManua.ls Logo

LG MULTI F LMU183HV - Page 14

LG MULTI F LMU183HV
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MULTI
F
MAX
MULTI
F
14
MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Multi F MAX Outdoor Unit Electrical Data
Nominal
Tons
Unit Model
No.
Phase Hertz Voltage
Voltage
Range
(Min. to
Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Outdoor Unit Fan Motor(s)
Indoor
Unit Fan
Motor
kW x Qty. FLA x Qty. FLA
4.0 LMU481HV
1 60 208 -230 187 - 253
32.7 40 1 22.0 2 x 0.12 1.60 x 2 4.0
4.5 LMU541HV 32.7 40 1 22.0 2 x 0.12 1.60 x 2 4.8
5.0 LMU601HV 32.7 40 1 22.0 2 x 0.12 1.60 x 2 5.2
Table 4: LMU481HV, LMU541HV, and LMU601HV Electrical Data.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as
IROORZV/DUJHVWPRWRU)/$[6XPRIRWKHUPRWRU
FLA) rounded down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.
Indoor Fan Motor (FLA) is based on the max. combination
of IDUs.

Table of Contents

Related product manuals