MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification. 
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI 
F
MAX
MULTI 
F
Using Refrigerant Components
Field-supplied elbows are allowed as long as they are designed for 
use with R410A refrigerant. The designer, however, must be cau-
tious with the quantity and size of fittings used, and must account 
for the additional pressure losses in equivalent pipe length calcula-
tion for each branch. The equivalent pipe length of each elbow must 
be added to each pipe segment. 
Table 12: Equivalent Piping Length for Elbows, Y-branches, and Branch 
Distribution Units.
5()5,*(5$176$)(7<67$1'$5'6
DEVICE CONNECTION LIMITATIONS
Component
Size (Inches)
1/4 3/8 1/2 5/8 3/4
Elbow (ft.) 0.5 0.6 0.7 0.8 1.2
Y-Branch Kit 
(ft., Multi F MAX systems only)
1
1.6
Branch Distribution Unit 
(ft., Multi F MAX systems only)
8.2
1
.LWFRQWDLQVWZR<EUDQFKHVRQHIRUOLTXLGDQGRQHIRUYDSRU
Example: LMU541HV outdoor unit with seven (7) 
indoor units, and two (2) branch distribution units 
connected.
ODU: Outdoor Unit.
IDU: Indoor Unit.
BD: Branch Distribution Unit(s).
A: Main Pipe.
B: Branch Pipe (Branch Distribution Unit[s] to Indoor Unit[s]).
B
A
h2 ≤ 49.2 feet
A
h3 ≤ 32.8 feet
h4 ≤ 49.2 feet
h1 ≤ 98.4 feet
BDU Y-Branch
BDU 
IDU 
A
ODU 
IDU 
IDU 
IDU 
IDU 
IDU 
IDU 
B
B
B
B
B
B
Pipe Length
(ELF = Equivalent 
Length of pipe in 
Feet)
7RWDOSLSLQJOHQJWKȉ$ȉ% IHHW
Main pipe (Outdoor Unit to 
Branch Distribution Units: 
A)
Minimum for Each 
(A) Piping Segment
16.4 feet
0D[LPXPȉ$ IHHW
7RWDOEUDQFKSLSLQJOHQJWKȉ% IHHW
Branch pipe (Branch
Distribution Units to Indoor 
Units: B)
Minimum  16.4 feet
Maximum IHHW
Elevation Differential
(All Elevation
Limitations are 
Measured in Actual 
Feet)
If outdoor unit is above or below indoor unit (h1) IHHW
Between the farthest two indoor units (h2) IHHW
Between branch distribution unit and farthest 
connected indoor unit(s) (h3)
IHHW
 Between branch distribution units (h4) IHHW
Max. Combination of 
IDUs
LMU481HV = 65,000 LMU541HV = 73,000 LMU601HV = 81,000
Piping Main Pipe A (inch) Branch Pipe B
Liquid Ø3/8
Depends on the size
of the indoor unit piping
Gas Ø3/4
Multi F MAX System Example with Two Branch Distribution Units
Multi F MAX Outdoor Unit Piping Length and Elevation Limitations
Table 13: Multi F MAX Refrigerant Piping System Limitations. 
h1
C
Branch Pipe
Main Pipe
BD Unit
BD Unit
A
B
h2
Figure 27: Multi F MAX Refrigerant Piping 
System Limitations.
Table 14:  Multi F MAX Piping Sizes.