38 Multi Air Conditioner
Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit
:
1. Use connection cable NRTL(UL, ETL, CAS…) listed and stranded copper(4) THHN conductors,
sunlight (UV) resistant ROHS compliant PVC jacket 600V direct burial listed, approved for wet
conditions. Temperature rated for –20℃(-4℉) to 90℃(194℉). And this cable should be enclosed
in conduit.
WARNING:
• Be sure to comply with local and national codes while running the wire from the indoor unit to the
outdoor unit(size of wire and wiring method, etc).
• Every wire must be connected firmly.
• No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.
• The communication wirings of air conditioner should be separate and isolated from external de-
viceʼs electric wiring such as computers, elevator, radio & Television broadcasting facilities, as
well as medical imaging offices.