EasyManua.ls Logo

LG Multi V 5 ARUV144DTE5 - Power Wiring Installation Precautions

LG Multi V 5 ARUV144DTE5
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Master Slave
Master Slave
Master Slave 1 Slave 2
Master Slave 1 Slave 2
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Multi-Core Cable
Master Slave
Master Slave
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Remote
control
Master Slave 1 Slave 2 Slave 3
Master Slave 1 Slave 2 Slave 3
Indoor
Unit
Indoor
Unit
Remote
control
Remote
control
Indoor
Unit
Indoor
Unit
22
ENGLISH
Master Slave 1 Slave 2
Master Slave 1 Slave 2
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Remote
control
Indoor
Unit
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal
block.
Round pressure terminal
Power cable
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal
block. (Slack in the power wiring may cause abnormal heat.)
- When connecting cable which is the same thickness, do as shown in
the figure below.
- For wiring, use the designated power cable and connect firmly, then
secure to prevent outside pressure being exerted on the terminal
block.
- Use an appropriate screwdriver for tightening the terinal screws. A
screwdriver with a small head will strip the head and make proper
tighterning impossible.
- Over-tightening the terminal screws may break them.
• Use the 2-core shielded wires for communication cables. Never use
them together with power cables.
• The conductive shielding layer of cable should be grounded to the
metal part of both units.
• Never use multi-core cable
• As this unit is equipped with an inverter, to install a phase leading
capacitor not only will deteriorate power factor improvement effect,
but also may cause capacitor abnormal heating. Therefore, never
install a phase leading capacitor.
• Make sure that the power unbalance ratio is not greater than 2 %.
If it is greater the units lifespan will be reduced.
CAUTION
!