LG Multi V 5 ARUV144DTE5 - Checking Outdoor Unit Settings; DIP Switch Setting Checks; Initial Display Check; Master;Slave DIP Switch Settings

LG Multi V 5 ARUV144DTE5
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
ENGLISH
It should be wiring power cables or communication cables to avoid
interference with the oil level sensor. Otherwise, That oil level sensor
would be operated abnormally.
Main power
terminal block
Insulation sleeves
attachments
Ground wire
Ground wire
ODU-IDU
Communication
cable
ODU-ODU
Communication
cable
Main power line
connection
Communication/Ground
wire connection
Checking the setting of outdoor units
Checking according to DIP switch setting
- You can check the setting values of the Master outdoor unit from the
7 segment LED.
The DIP switch setting should be changed when the power is OFF.
Checking the initial display
The number is sequentially appeared at the 7 segment in 5 seconds
after applying the power. This number represents the setting condition.
[Main Board]
DIP switch
7 segment
SW01C
(Automatic Addressing Setting)
Quick control Setting
In the factory setting, main PCB DIP switch setting is all “OFF”.
- Check and make sure that all the indoor unit model name are
ARNU******4.
- Change the main PCB DIP switch No. 3 “OFF ON” like below
picture.
- Push the reset button.
7 segmentDIP Switch
Reset button
• Initial display order
• Example) ARUV603BTE(R)5 (50RT)
60 hp 220 V Cooling Only System (Master unit: 18 HP(14 RT),
Slave 1: 14 HP(12 RT), Slave 2: 14 HP(12 RT),
Slave 3: 14 HP(12 RT))
Order No Mean
10(8RT)~26(22RT) Master unit capacity
12(10RT)~24(20RT) Slave 1 unit capacity
12(10RT)~24(20RT) Slave 2 unit capacity
12(10RT)~24(20RT) Slave 3 unit capacity
10(8RT)~96(80RT) Total capacity
1 Cooling Only
38 380V model
46 460V model
22 220V model
50 Product type
18 14 14 14 60 1 22 50
HP 10 12 14 18 20 22 24 26
RT 8 10 12 14 16 18 20 22
Master/Slave DIP switch setting
• Master Unit
• Slave Unit
DIP switch
setting
ODU Setting
Slave 1
Slave 2
Slave 3
DIP switch
setting
ODU Setting
Factory Setting
CAUTION
!