GENERAL DATA
Electrical Low-Static Built-In B3/B4 Chassis
Table 11: Low-Static Built-In B3/B4 Chassis Electrical Data.
Model Voltage Range MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
B3 Units
ARNU073B3G4
187-253
1.0
15
0.76
60 208-230 1
85 85
ARNU093B3G4 1.0 0.76 85 85
ARNU123B3G4 1.0 0.76 85 85
ARNU153B3G4 1.0 0.76 85 85
B4 Units
ARNU183B4G4
187-253
1.2
15
0.97
60 208-230 1
115 115
ARNU243B4G4 1.2 0.97 115 115
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.