WIRING
Table 33:  Low-Static Built-In B3/B4 Chassis Wiring Diagram
Low-Static Built-In B3/B4 Chassis
CONNECTOR PURPOSE FUNCTION
CN-POWER
AC Power supply AC Power line
CN-MOTOR1
Fan motor output Motor output of BLDC
CN-MOTOR2
Fan motor output Motor output of BLDC
CN-VM
Sub PC power supply Power supply connection
CN-FLOAT
Float switch input Float switch sensing
CN-ZONE
Zone controller Zone controller connection
CN-EEV
EEV Output EEV control output
CN-OPTION
Optional PCB EPROM Option PCB connection
CN-EXT
External ON / OFF controller External ON / OFF controller connection
CN-DISPLAY
Display Display of indoor status
CN-CC
Dry contact Dry Contact connection
CN-PTC
Auxiliary heater Connection for Auxiliary Heater
CN-PIPE/OUT
Discharge pipe sensor Pipe out thermistor
CN-LEAK
Refrigerant leak detector Refrigerant leak detector connection
CN-PIPE/IN
Suction pipe sensor Pipe in thermistor
CN-REMO
Wired remote controller Wired remote control connection
CN-ROOM
Room sensor Room air thermistor
CN-D/PUMP
Drain pump output AC output for drain pump
CN-485
Communication Connection between indoor and outdoor units
Table 34: B3, B4 Unit DIP Switch Settings.
*For Gen 4 Multi V ducted indoor units, DIP switches 1, 2, 6 through 8 must be set to OFF.  These DIP switches are used for 
other models. 
**To enable Generation 4 features, outdoor unit DIP Switch No. 3 must be set to ON. Please refer to the Multi V IV, Multi V Wa-
ter IV, Multi V S Engineering Manual for additional information.
DIP Switch Setting Off On Remarks
SW3
GROUP CONTROL Master Slave
Group control setting using 7-Day Programmable Controller; selects Master / 
Slave on each indoor unit
SW4
DRY CONTACT 
MODE
Variable Auto
Sets operation mode for optional Dry Contact accessory
1. Variable: Auto or Manual Mode can be set through 7-Day Programmable
Controller or Wireless Remote Controller (factory default setting is Auto if 
there is no setting)
2. Auto: For Dry Contact, it is always Auto mode
SW5
CONTINUOUS FAN Off On
Selects continuous fan for ducted indoor units.
1. On: Indoor unit fan will always operate at a set fan speed, except when 
the system is off, or the outdoor unit is in defrost mode (when the oudoor unit 
is in defrost mode, the fan will operate at super low fan speed)
2. Off: Indoor unit fan speed can be changed by on / off