Troubleshooting Guide
- 116 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
n Error diagnosis and countermeasure flow chart
n Check Inverter PCB Screw Connection Condition
Error No. Error Type Error Point Main Reasons
62*
Master 621
Slave1 622
Slave2 623
Slave3 624
Inverter PCB Heatsink 
Temperature High
Heatsink Temperature
is Over 90°C
1. Inverter PCBA IPM Connection Condition Abnormal
2. Outdoor Unit Fan Motor Operation Abnormal
3. Outdoor Unit Inverter PCB Assembly Defect
4. Overload Operation (Pipe Clogging/ Covering/EEV
Defect/Ref. Overcharge)
Is Installation 
Condition Normal? 
No 
1. Check Pipe Clogging/ Distortion 
2. Check Covering (Outdoor/Indoor Unit) 
3. Check EEV Connector Assemble Condition/Normal Operation 
4. Check Refrigerant Pressure 
5. Check Power Wire/ Connection Condition 
   Reassemble or Manage if abnormality Found 
1. Check Inverter PCBA Screw Connection Condition 
   Reassemble or Manage if abnormality Found 
No 
Inverter PCB IPM Connection 
Condition Normal? 
Yes 
1. Check Outdoor Unit Fan Motor Operation or Lock  
   Reassemble or Manage if abnormality Found 
No 
Is ODU Fan Motor Normal? 
Yes 
1. Reset    
   Replace Inverter PCB Assembly 
No 
Is Inverter PCB assembly  
Normal? 
Yes 
Recheck Power and 
Installation Condition 
Yes 
Check Screw