4.9 Multi V ITR result report
Follow the process.
Save html file
Multi V Start up Confirmation
Date
Person In
Charge
Company Name & Address Telephone Name
Installer
Consultant
Supervisor
Product
Model Model No. Position
Outdoor Unit
Indoor Unit
HR Unit
Test Run Results
Operation Mode %ITR_6 All IDU Operation 1 IDU Operation STEP %ITR_122
Check Items Min. Max. Average Min. Max. Average OK/NG Criterion For Judgment
Temp.
Condition
IDU Air Temp 20~30°C
ODU Air Temp
Indoor Unit
IDU pipe inlet Temp
IDU pipe outlet temp
IDU LEV Openess
Outdoor Unit
Pressure
High Pressure
3,600kPa (Cool)
2,300kPa (Heat)
Low Pressure
1,300kPa (Cool)
200kPa (Heat)
COMP
COMP Operate Combination
CT Value
ODU #1 Comp1
24A
ODU #1 Comp2
ODU #2 Comp1
ODU #2 Comp2
ODU #3 Comp1
50°C ~ 100°C
ODU #3 Comp2
ODU #4 Comp1
ODU #4 Comp2
Discharge
Temp.
ODU #1 Comp1
ODU #1 Comp2
ODU #2 Comp1
ODU #2 Comp2
ODU #3 Comp1
ODU #3 Comp2
ODU #4 Comp1
ODU #4 Comp2
Main Voltage
R-phase 342~456 V
T-phase
Main Current
R-phase
20A
T-phase
Discharge
Superheat
ODU #1
10°C ~ 50°C(Heat)
ODU #2
ODU #3
ODU #4
Suction
Superheat
ODU #1
0.5°C (Cool) 0.5°C~7°C
(Heat)
ODU #2
ODU #3
ODU #4
ODU LEV
Openness
ODU #1
ODU #2
ODU #3
ODU #4
Refrigerant Check
Main EEV Check
IDU EEV Check
Function

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V IV ARNU07GTU 2 Series and is the answer not in the manual?

LG MULTI V IV ARNU07GTU 2 Series Specifications

General IconGeneral
BrandLG
ModelMULTI V IV ARNU07GTU 2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals