Troubleshooting Guide
- 123 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1.Fan motor defect/ assemble condition abnor-
mal
2.Fan motor connector misconnection(U,V,W
ouput)
3.Fan PCB defect
Error No. Error Type Error Point Main Reasons
Fan Motor initial starting failure
Fan Starting Failure
Error
79*
Master 791
Slave1 792
Slave2 793
Slave3 794
n Error Diagnosis and Countermeasure Flow Chart
Is fan motor connection
condition normal?
1. Check if color of motor output terminal(U,V,W) connector matched with PCBs
2. Check wire disconnection and wiring
Reassemble or replace if abnormality found
Is fan PCB assembly normal?
Yes
No
Recheck power and
installation condition
Yes
No
1.Check resistance between each motor output terminal
LG motor : 8.8Ω±10%(25℃)
Panasonic : 8.8Ω±10%(25℃)
2. Check insulation resistance between ODU fan motor terminal(U,V,W) and pipe (over 100M )
Replace fan motor if abnormality found
No
Are the resistance
Between each phase and insulation
resistance of motor output
terminal normal?
Check ODU fan motor assemble condition and locking
Reassemble or replace if abnormality found
No
Is fan motor assemble
condition normal?
Fan motor wire connection
Measuring fan motor
phase resistance
Check fan PCB assembly IPM normal
Replace Fan PCB assembly
Check
Point
Measuring insulation resistance
between fan terminal & chassis