PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
41
ENGLISH
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe and
CF(correction Factor) value of indoor unit.
Additional charge(kg) = Total liquid pipe : Ø 12.7 mm x 0.118(kg/m)
+ Total liquid pipe : Ø 9.52 mm x 0.061(kg/m)
+ Total liquid pipe : Ø 6.35 mm x 0.022(kg/m)
+ CF value of indoor unit (kg)
Amount refrigerant of Indoor units
Example) 4 Way Ceiling Cassette 14.5 kW - 1 ea, Ceiling concealed Duct 7.3 kW - 2 ea,
Wall Mounted 2.3 kW - 4 ea
CF = 0.64 × 1 + 0.26 × 2 + 0.24 × 4 = 2.12 kg
Attach the additional refrigerant table of IDU.