AI
10-2
0 0 0.4
Comp.
off
----
DO 01-4 is short,
DO 01-2 is open.
1 0.6 1.4
Comp.
off
----
2 1.6 2.4 40 1,160 20.3 1,800 28.4
DI will determine
fan mode and
opeation mode
3 2.6 3.4 45 1,100 19.0 1,950 31.5
4 3.6 4.4 50 1,070 17.9 2,080 34.1
5 4.6 5.4 60 990 15.8 2,340 38.9
6 5.6 6.4 70 930 14.0 2,560 42.5
7 6.6 7.4 80 870 12.5 2,730 45.1
8 7.6 8.4 90 830 11.3 2,990 49.0
9 8.6 9.4 100 800 10.5 3,000 49.2
10 9.6 10 100 800 10.5 3,000 49.2
AHU KIT WIRING CONFIGURATION WITH DDC
27
ENGLISH
AI
No.
Input
voltage
[Vdc]
Low
[Vdc]
High
[Vdc]
Capacity
of unit
[%]
Cooling
Heating
Control
Target
Low
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
Target
High
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
AI
No.
Input
voltage
[Vdc]
Low
[Vdc]
High
[Vdc]
Capacity
of unit
[%]
Cooling
Heating
Control
Target
Low
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
Target
High
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
2. Option #2
3. Option #3
AI
10-2
0 0 0.4
Comp.
off
----
DO 01-4 is short,
DO 01-2 is open.
1 0.6 1.4 40 1160 20.3 1800 28.4
DI will determine
fan mode and
opeation mode
2 1.6 2.4 45 1100 19.0 1950 31.5
3 2.6 3.4 50 1070 17.9 2080 34.1
4 3.6 4.4 60 990 15.8 2340 38.9
5 4.6 5.4 70 930 14.0 2560 42.5
6 5.6 6.4 80 870 12.5 2730 45.1
7 6.6 7.4 90 830 11.3 2990 49.0
8 7.6 8.4 100 800 10.5 3000 49.2
9 8.6 9.4 100 800 10.5 3000 49.2
10 9.6 10 100 800 10.5 3000 49.2