Address NO. Description Default Maximum Minimum Unit
5355 FU2 #85
2nd F-boost 20 150 0 0.1%
5356 FU2 #86
2nd R-boost 20 150 0 0.1%
5357 FU2 #87
2nd Stall 150 150 30 %
5358 FU2 #88
2nd ETH 1min 150 200
2nd ETH
Cont
%
5359 FU2 #89
2nd ETH Cont. 100
2nd ETH
1min
50 %
535A FU2 #90
2nd R-Curr 36 2000 10 0.1A
535D FU2 #93
Para. Init 0 8 0
(Note 4, 5, 6, 7) Value depends on motor capacity.
< I/O Group >
Address NO. Description Default Maximum Minimum Unit
5401 I/O #01
V1 filter 10 9999 0 ms
5402 I/O #02
V1 volt x1 0 V1 vort x2 0 0.01V
5403 I/O #03
V1 freq y1 0 maxFreq 0 0.01Hz
5404 I/O #04
V1 volt x2 1000 1000 V1 volt x1 0.01V
5405 I/O #05
V1 freq y2 6000 maxFreq 0 0.01Hz
5406 I/O #06
I filter 10 9999 0 ms
5407 I/O #07
I curr x1 400 I curr x2 0 0.01mA
5408 I/O #08
I freq y1 0 maxFreq 0 0.01Hz
5409 I/O #09
I curr x2 2000 2000 I curr x1 0.01mA
540A I/O #10
I freq y2 6000 maxFreq 0 0.01Hz
540B I/O #11
Wire broken 0 2 0
540C I/O #12
P1 define 0 32 0
540D I/O #13
P2 define 1 32 0
540E I/O #14
P3 define 2 32 0
5411 I/O #17
Ti Filt Num 15 50 2
5414 I/O #20
Jog freq 1000 MaxFreq startFreq 0.01Hz
5415 I/O #21
Step freq - 4 4000 MaxFreq startFreq 0.01Hz
5416 I/O #22
Step freq - 5 5000 MaxFreq startFreq 0.01Hz
5417 I/O #23
Step freq - 6 4000 MaxFreq startFreq 0.01Hz
5418 I/O #24
Step freq - 7 3000 MaxFreq startFreq 0.01Hz
5419 I/O #25
Acc time– 1 200 6000 0 0.1sec
541A I/O #26
Dec time – 1 200 6000 0 0.1sec
541B I/O #27
Acc time – 2 300 6000 0 0.1sec
541C I/O #28
Dec time – 2 300 6000 0 0.1sec
541D I/O #29
Acc time – 3 400 6000 0 0.1sec