modbus-rtu iS5 manual.doc
14
< COM Group >
Address NO. Description Default Maximum Minimum Unit
5601 COM #01
Opt B/D
5602 COM #02
Opt mode 0 3 0
5603 COM #03
Opt version 1.00
Note) Inverter Station # and Baud rate Setting: I/O-46, 47
COM-01 [Opt B/D]
Indicates Option boards installed. This value is automatically set when the boards are installed.
COM-02 [Opt Mode]
Determines whether Run/Stop/Reference Frequency is set via Communication.
Value Display Description
0 None Disabled
1 Command Run/Stop setting via Communication
1
2 Freq Frequency setting via Communication
2
3 Cmd + Freq Run/Stop/Reference Frequency via Communication
COM-03 [Opt Version]
Displays version of Option Board.
< APP Group >
Address NO. Description Default Maximum Minimum Unit
5701 APP #01
APP mode 0 3 0
5702 APP #02
Trv. Amp [%] 0 200 0 0.1%
5703 APP #03
Trv. Scr 0 500 0 0.1%
5704 APP #04
Trv Acc Time 20 6000 1 0.1sec
5705 APP #05
Trv Dec Time 30 6000 1 0.1sec
5706 APP #06
Trv Off Hi 0 200 0 0.1%
5707 APP #07
Trv Off Lo 0 200 0 0.1%
5708 APP #08
Aux Mot Run 0 4 0
5709 APP #09
Starting Aux 1 4 1
570A APP #10
Auto Op Time 0 5940 0
570B APP #11
Start freq1 4999 maxFreq 0 0.01Hz
570C APP #12
Start freq2 4999 maxFreq 0 0.01Hz
570D APP #13
Start freq3 4999 maxFreq 0 0.01Hz
570E APP #14
Start freq4 4999 maxFreq 0 0.01Hz
570F APP #15
Stop freq1 1500 maxFreq 0 0.01Hz
1
Run/Stop Setting Address - Use 0x0006 in Common
2
Freq Setting Address - Use 0x0005 in Common