System Set-Up
Installation Manual 83
ENGLISH
Code Item Detail Remark
2B
2E
2F
42
Function Domestic hot water heating timers
Description
Value #1 Note
Default
Range 5 ~ 95 min (step: 5 min)
Value #2 Note
Default
30 min
Range 0 ~ 600 min (step: 30 min)
180 min
Determine following time duration : operation time of Domestic hot
water tank heating, stop time of Domestic hot water tank heating,
and delay time of sanitary tank heater operating.
This time duration defines how long time Domestic hot water tank
heating can be stopped. It is also regarded as time gap between
Domestic hot water tank heating cycle.
Value #3 Note
Default
Range 20 ~ 95 min (step: 5 min)
20 min
This time duration defines how long time Domestic hot water tank
heater will not be turned on in Domestic hot water heating operation.
This time duration defines how long time Domestic hot water tank
heating can be continued.
2A
Function Miscellaneous setting
Description Determine electric heater and water heater on and off
Value #1 Note 00: Operate both electric heater and Domestic hot water tank heater
01: Operate only Domestic hot water tank heater
Default 00
Range 00 ~ 01
Value #2 Note Not used
Default -
Range -
Function Changing thermal on / off room air temp
Description Select Thermal on / off Temperature gap.
Value #1 Note
0
1
2
3
-0.5 °C
4 °C
2 °C
-1 °C
1.5 °C
6 °C
4 °C
1 °C
Thermal on Thermal off
Default
0
Range
0 ~ 3
Function Changing thermal on / off leaving water Ten
Setting mode lock function
Mode-lock is can operate only cooling
00 (Not use Mode-lock)
00~01
Description Select Thermal on / off Temperature gap.
Value #1 Note
0
1
2
3
-2 °C
-6 °C
-2 °C
-1 °C
2 °C
4 °C
4 °C
1 °C
Thermal on Thermal off
Default
0
Range
Function
Description
Default
Range
0 ~ 3
Note: Some contents may not be displayed depending on DIP switch setting in the main PCB assembly 1.