THERMA V Split Type
6. Performance Data
20
Outdoor unit
AHUW148A3 [HU143 U33] + AHNW16606B0 [HN1616T NB0]
AHUW168A3 [HU163 U33] + AHNW16606B0 [HN1616T NB0]
Note
1. DB : Dry bulb temperature(), LWT : Leaving water temperature()
2. TC : Total capacity(kW), PI : Power Input(kW)
3. Direct interpolation is permissible. Do not extrapolate.
4. Measuring procedure follows EN-14511.
• Rated values are based on standard conditions, and it can be found on specifications.
• Above table values may not be matched according to installation condition. Except for rated value, the performance is not guaranteed.
• In accordance with the test standard(or nations), the rating will vary slightly.
Outdoor
Temperature
LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20 DB
7.43 2.58 8.53 2.60 9.62 2.62 10.35 2.64 11.45 2.66 12.18 2.68 - -
30 DB
7.24 3.14 8.31 3.17 9.37 3.19 10.08 3.21 11.15 3.24 11.86 3.26 - -
35 DB
7.14 3.42 8.19 3.45 9.25 3.48 9.95 3.50 11.00 3.53 11.70 3.55 12.40 3.57
40 DB
7.05 3.70 8.08 3.73 9.12 3.77 9.81 3.79 10.85 3.82 11.54 3.84 12.23 3.86
45 DB
6.95 3.98 7.97 4.02 8.99 4.05 9.68 4.07 10.70 4.11 11.38 4.13 12.06 4.16
Outdoor
Temperature
LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20 DB
8.11 2.92 9.30 2.95 10.50 2.97 11.30 2.99 12.49 3.02 13.29 3.03 - -
30 DB
7.90 3.56 9.06 3.59 10.22 3.62 11.00 3.64 12.16 3.67 12.94 3.69 - -
35 DB
7.79 3.87 8.94 3.91 10.09 3.94 10.85 3.97 12.00 4.00 12.77 4.02 13.53 4.05
40 DB
7.69 4.19 8.82 4.23 9.95 4.27 10.70 4.29 11.84 4.33 12.59 4.35 13.35 4.38
45 DB
7.58 4.51 8.70 4.55 9.81 4.59 10.56 4.62 11.67 4.66 12.42 4.68 13.16 4.71