7
Single CAC Outdoor Unit
Standard Inverter - Synchro
4. Piping Length & Height
Synchro Operation
Install the branch pipe so that pipe length and difference between high and low will not exceed below Spec.
[Unit : m]
When installing the branch pipe, direction and angle of installation is not limited.
Take care so that burrs and foreign material may not enter into the cutting surface when connecting.
Connect remaining those by cutting or direct insertion to the diameter of pipe.
Pipe Length & Height Spec(MAX.)
Total(L1+L2+L3+L4+L5)
Main Pipe(L1)
Branch Pipe (L2+L3+L4+L5)
Each
Indoor-Outdoor (H1)
Indoor-Indoor (H2)
L6
80
45
40
15
30
1
10
Indoor Unit
Indoor Unit
Indoor Unit
Indoor Unit
L1
L2
L3
L4
L5
L6
H2
H1
Branch
Notes
L1 (m) : Main Piping Length (Outdoor Unit ~ Branching Kit)
L2~L5 (m) : Branch Piping Length (Branching Kit ~ Indoor Unit)
L6 (m) : Length Difference (the Nearest Indoor Unit ~ the farthest Indoor Unit)
H1 (m) : Height Difference (Outdoor Unit ~ Indoor Unit)
H2 (m) : Height Difference (Indoor Unit ~ Indoor Unit)
Refer to the specifications of Outdoor Unit for Maximum limit.