Why is the Liebert Fan compressor motor protectors tripping or cycling?
- EeharrisAug 19, 2025
The Liebert Fan compressor motor protectors might be tripping or cycling due to several reasons. High discharge pressure could be the cause, so check for a blocked condenser fan or coil. High suction temperature is another possibility; in this case, inspect the expansion valve and hot gas bypass valve settings, and check the liquid quenching valve operation. Also, inspect for loose power or control circuit wiring connections. Finally, a defective motor can cause this issue; check for a motor ground or short, and replace the compressor if either condition is found.