10
U33 Dripping water time
0180min
5
11
U34
Over temperature warning delay time
after defrost ends
0~180 hour 0: Disable 2
12
U35 Defrost when the device starts 0~1
0: Disable
1:Enable
0
13
U36
Defrost delay time when the device
start
0180min
0: Disable 0
14
U40 Fan start temperature
-45+120
-10
15
U41 Fan start-up delay
0600sec
60
16
U42 Fan stop delay
0600sec
0
17
U43 Fan mode
01
0: Controlled
1: Free mode
0
18
U50
High-temperature warning deviation
value to Max Temp
0~60 0: Disable 0
19
U51
Low-temperature warning deviation
value to Min Temp
0~60 0: Disable 0
20
U52 Over-temperature warning delay time
1180min
30
21
U53
First over-temperature warning delay
time after power supply
0~180 hour 0: Disable 2
22
U60 External input warning mode 0~4
0:Warning off
1:On, Lock
2:On, Unlock
3:Off, Lock
4:Off, Unlock
0
23
U61
External warning input delay
0~120min 0
24
U62 Buzzer warning 0~1
0:Warning off
1:Warning on
25
U97 Baud rate setting 0 ~ 3
0: 2400bps
1: 4800bps
2: 9600bps
3: 19200bps
3
26
U98 Device address 1 ~ 99 ---- 1
27
U99 Password 0000~9999 1111
28
End Finished setting
7. Control Function Description
7.1 Compressor Control
When the temperature “Set temperature”+”U22”, and the compressor has stopped for
“U10”, the compressor starts.
When the temperature “Set temperature” -”U22”, and the compressor has run for “U11”,