High temperature warning point
Exhaustion temperature up limit
Start exhausting for cooling
Exhaustion temperature low limit
Main temperature up limit
Main heater stops heating
Main temperature low limit
Main heater starts heating
Aux temperature low limit
Aux heater starts heating
Low temperature warning point
High humidity warning point
Humidify load stops humidifying
Humidify load starts humidifying
Exhaustion humidity up limit
Start ventilation for de-humidifying
Exhaustion humidity low limit
Stop de-humidifying ventilation
Over wet exhaustion protection
Low humidity warning point
Set function control parameter
Press【Set】and【▼】simultaneously to enter into function control parameter setting status.
Press【Enter】to select parameter.
SV window displays the selection from “***” + “F1” to “***” + “FF”.
Press【▲】or【▼】to set the value of the parameter (Keeping the key depressed can fast set).
Keeping【Enter】depressed for 2 seconds will exit setting status, the settings will be saved.
The setting status will exit without saving, if there is no key operation for 15 seconds.
Function control parameter code table:
0: no egg turning function
0: no illuminating function
Check Incubated Days and Egg Turned Counter
Press【Enter】and【▲】simultaneously, SV window displays〖incubated days, FF〗“days” + “t1” for 2 seconds.
Press【Enter】and【▼】simultaneously, SV window displays egg-turned-counter “times” + “t2” for 2 seconds.
Control and Operation
On/off operation
Keep【Lamp - I/O】depressed for 2 seconds, controller turns on or off.
Illumination operation
Manual on/off: Press【Lamp - I/O】, lamp turns on or off.
Timer on/off: For every〖Illumination period, F8〗, lamp will be on for〖Illumination time, F9〗.
Temperature control
Main heater: When room temperature ≤〖Main temperature low limit, P4〗, the main heater will be on.
When room temperature ≥〖Main temperature up limit, P3〗, the main heater will be off.
Aux. heater: When room temperature ≤〖Aux temperature low limit, P6〗, the aux. heater will be on.
When room temperature ≥〖Aux temperature up limit, P5〗, the aux. heater will be off.
Temperature and humidity control parameter code table: