This appliance must be installed, commissioned, serviced and converted by a
qualified person in accordance with national and local regulations in force in the
country of installation.
Install this appliance on a level surface ensuring all vents are unobstructed.
Minimum distances – see Fig 1, A 50mm B 1000mm.
R
½
(½” BSP
Fig 1
Site this appliance beneath an extraction canopy for the removal of combustion
products.
Installation must include sufficient ventilation to prevent the occurrence of
unacceptable concentrations of substances harmful to health in the room of
installation. There must be a minimum free area of 4.5cm
2
per kW of total heat
input.
Allow for a sufficient flow of fresh air for complete gas combustion.