EasyManua.ls Logo

Lite-Puter DX-626 - Safety Introduction; The Load Power; Working Environment; Suggested Dimming Lights

Lite-Puter DX-626
11 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ISO9001CERTIFIED
www.liteputer.com.tw
Lite-Puter
DX-610/626[EUM-
]
2
SAFETYINTRODUCTION
TheLoadPower
Pleaserefertothedatawesuggestedtoensurethenormaltotalworkinghours
ofDX-610/DX-626
1. IfDX-610/DX-626isinstalledinarack,pleasemakesuretherackisairy.
Otherwisethemachinewillbecomeover-heatandresultinthe
mis-function.
2. DX-610:themax.outputofeachchannelis10A:Fortesting(DONotover30
minutes)
DX-626:themax.outputofeachchannelis20A:Fortesting(DONotover
30minutes)
3. DX-610:theoutputofeachchannelisŊ8A:Forseveralhoursuse(Theaters,
Stages)
DX-626:theoutputofeachchannelis16A:Forseveralhoursuse
(Theaters,Stages)
4. DX-610:theoutputofeachchannelis 8A:Canworkforthewholeyear
withoutswitchingoff(Hotels,Restaurants,Buildings)
DX-626:theoutputofeachchannelis 12A:Canworkforthewholeyear
withoutswitchingoff(Hotels,Restaurants,Buildings)
WorkingEnvironment
1. Temperature Under35°C
2. Ifthemachineisinstalledinarack,thenthetemperatureinsidetherack
mustbeunder45°C
3. Humidity40%---80%
SuggestedDimmingLights
Incandescentlamps,halogenlamps,lowvolthalogenlampswithballast.

Related product manuals