11 
 
Over torque/torque shortage detection, multi-speed operation, 
acceleration/deceleration switching, instantaneous power failure restart, 
speed search, S-curve acceleration/deceleration, 3-wire sequential 
control, motor parameter automatic detection, cooling fan ON/OFF 
function, sliding Differential compensation, torque compensation, 
frequency jump, frequency command upper and lower limit setting, DC 
braking at start/stop, PID control, fault retry, automatic voltage 
adjustment. 
Indoor without corrosive gas/liquid or flammable gas/liquid/oil mist/dust 
-10℃  to +50℃, below 90% RH without froze or condensation 
Below 9.8 m/s
2
 (10 to 20Hz), below 5.9 m/s
2
 (20 to 55Hz) 
1 point (AI: 0 to 5V, 0 to 10V (12 bits),    0 or 4 to 20mA(11 bits)) 
1 point (FM: 0 to 10V (10bits)) 
Profibus-DP, CANopen, DeviceNet 
The drive is suitable for use in a circuit capable of delivering not more 
than 5,000 rms symmetrical amperes, 480 Volts Maximum. 
UL 508C, CSA C22.2 no .274, IEC 61800-5-1, IEC 61800-3 
*1. Results tested in labs