38
F1:80000000
Internal OVP3
F2:00000001
Grid Grounding Fault
Check the grounding wire.
F2:00000002
L/N Reversely Connected
Check the L/N wire.
F2:00000004
Insulation Fault
Check the insulation of PV panels.
F2:00000008
RCMU Fault
Check the PV Panels.
F2:00000010
Grid Relay Fault
These errors will reset itself. If it
keeps coming and finally the Inverter
is latched up, please contact with
your local distributor.
F2:00000020
EPS Relay Fault
F2:00000040
Bypass Relay Fault
F2:00000080
EEPROM1 Error
F2:00000100
Single Faults
F2:00000200
Internal Comm. F1
F2:00000400
Internal Comm. F2
F2:00000800
Internal Comm. F3
F2:00001000
PV1 Reversed
Check the PV terminals, confirm the
positive and negative polarity and
re-wire.
F2:00002000
PV2 Reversed
Error Code Description Solution
F3:00000001
BMS External Fault
Check the battery for parameter
settings. Contact with your local
battery’s distributor.
F3:00000002
BMS Internal Fault
F3:00000004
BMS OVP
F3:00000008
BMS UVP
F3:00000010
BMS Charge OCP
Check the battery for parameter
settings. Contact with your local
battery’s distributor.
F3:00000020
BMS Discharge OCP
F3:00000040
BMS OTP
F3:00000080
BMS UTP
F3:00000100
Cell Imbalance
F3:00000200
BMS Reversed
Confirm the positive and negative
polarity and re-wire.
F3:00000400
Meter Comm. Fault
Please check the communication
cable for smart meter. If using
cable other than what is included,
a 1000-ohm resistor should be
connected to the meter.
F3:00000800
Internal Comm. F5
These errors will reset itself. If it
keeps coming and finally the
Inverter is latched up, please
contact with your local distributor.
F3:00001000
Internal Comm. F6
F3:00002000
EEPROM2 Error
F3:00004000
BMS Communication fault.
Check whether the BMS line is
plugged in well, and whether the
BMS line is in good condition, it is
recommended to make a new
communication line if possible.
F3:00008000
Firmware fault
First, disconnect the power and
restart. If the problem cannot be
solved after restarting, please
contact with the distributor.