Lonza • 1200 Lower River Road, P.O. Box 800 • Charleston, TN 37310-0800 • 1-800-4-PULSAR
4
rev.3 (3/12/14)
Operational Requirements:
Inlet pressure (Range) ................................... 35-45 psi [2.41-3.10 bar]
Ideal ................................................ 37 psi [2.55 bar]
Outlet vacuum ........................................ 15-29” Hg. [38.1-73.7cm]
Operating Temperature .................................. 40-115ºF [4.4º to 46.1º C]
Supply power ......................................... 110V, 15A (NEMA 5-15R)
Operational Characteristics:
Inlet flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.75 gpm [2.84 lpm]
Outlet flow ........................................... 2.5 gpm [9.46 lpm]
Dimensions:
Tubing .............................................. 1/2” [12.7mm] O.D. Polyethylene
Chlorinator dimensions .................................. W: 25” [63.5cm] x D: 30” [76.2 cm]
Chlorinator height ...................................... 35” [88.9cm]
Chlorinator weight (full) .................................. 150 lbs [68.0kg]
Chlorinator weight (empty) ............................... 50 lbs [22.7kg]
Capacity:
100 lbs [45.4kg] Pulsar
®
Plus Dry Chlorinator Briquettes (equivalent to 68 lbs [30.8kg] available chlorine)
Feed Rate:
Pulsar
®
Plus Briquettes: 8-163 lbs [3.7-73.9kg] of Available Chlorine per day
Recommended Pool Size
1
:
15,000-200,000 gallon [56,781-757,082 liter] un-stabilized
1
50,000-600,000 gallon [189,271-2,271,247 liter] stabilized
1
1
Subject to local health codes
SPECIFICATIONS – Model PS 140