Chapter 5 - Parameter List
59
Keypad Display Setting Range
Code Description
LCD 7-Segment
LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
FU1-27
Torque Boost in Forward
Direction
Fwd boost 27 0 to 15 [%] 0.1
2.0 [%] No
FU1-28
Torque Boost in Reverse
Direction
Rev boost 28 0 to 15 [%] 0.1
2.0 [%] No
Linear 0
Square 1
FU1-29
Volts/Hz Pattern V/F pattern 29
User V/F 2
- Linear No 93
FU1-30
16
User V/F – Frequency 1
User freq 1 30 0 to FU1-20 0.01
15.00 [Hz]
No
FU1-31
User V/F – Voltage 1 User volt 1 31 0 to 100 [%] 1 25 [%] No
FU1-32
User V/F – Frequency 2
User freq 2 32 0 to FU1-20 0.01
30.00 [Hz]
No
FU1-33
User V/F – Voltage 2 User volt 2 33 0 to 100 [%] 1 50 [%] No
FU1-34
User V/F – Frequency 3
User freq 3 34 0 to FU1-20 0.01
45.00 [Hz]
No
FU1-35
User V/F – Voltage 3 User volt 3 35 0 to 100 [%] 1 75 [%] No
FU1-36
User V/F – Frequency 4
User freq 4 36 0 to FU1-20 0.01
60.00 [Hz]
No
FU1-37
User V/F – Voltage 4 User volt 4 37 0 to 100 [%] 1 100 [%]
No
94
FU1-38
Output Voltage
Adjustment
Volt control 38 40 to 110 [%] 0.1
100.0 [%]
No 94
FU1-39
Energy Save Level Energy save 39 0 to 30 [%] 1 0 [%] Yes
94
No 0
FU1-50
Electronic Thermal
Selection
ETH select 50
Yes 1
- No Yes
FU1-51
17
Electronic Thermal Level
for 1 Minute
ETH 1 min 51 FU1-52 to 200 [%] 1 180 [%]
Yes
FU1-52
Electronic Thermal Level
for Continuous
ETH cont 52 50 to FU1-51 (Maximum 150%) 1 120 [%]
Yes
Self-cool 0
FU1-53
Electronic Thermal
Characteristic Selection
(Motor Type)
Motor type 53
Forced-cool 1
- Self-cool
Yes
95
FU1-54
Overload Warning Level
OL level 54 30 to 150 [%] 1 150 [%]
Yes
FU1-55
Overload Warning Hold
Time
OL time 55 0 to 30 [sec] 0.1
10.0 [sec]
Yes
96
No 0
FU1-56
Overload Trip Selection OLT select 56
Yes 1
- Yes Yes
FU1-57
Overload Trip Level OLT level 57 30 to 200 [%] 1 180 [%]
Yes
FU1-58
Overload Trip Delay Time
OLT time 58 0 to 60 [sec] 1 60.0 [sec]
Yes
96
FU1-59
Stall Prevention Mode
Selection
Stall prev. 59
000 to 111
(Bit Set)
bit 000 No
FU1-60
Stall Prevention Level Stall level 60 30 to 250 [%] 1 180 [%]
No
97
FU1-99
Return Code Not displayed
99 Not available 1 - 1 - 98
16
Code FU1-30 through FU1-37 appears only when FU1-29 is set to ‘User V/F’.
17
Code FU1-51 through FU1-53 appears only when FU1-50 is set to ‘Yes’.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LS SV037iS5-4 and is the answer not in the manual?

LS SV037iS5-4 Specifications

General IconGeneral
BrandLS
ModelSV037iS5-4
CategoryController
LanguageEnglish

Related product manuals