Chapter 6 - Parameter Description [FU1]
89
[[Stop Mode: ‘Free-run’]
FU1-08: DC Injection Braking Frequency
FU1-09: DC Injection Braking On-delay Time
FU1-10: DC Injection Braking Voltage
FU1-11: DC Injection Braking Time
By introducing a DC voltage to the motor windings this
function stops the motor immediately. Selecting ‘DC-
Brake’ in FU1-07 activates FU1-08 through FU1-11.
FU1-08 [DC Injection Braking Frequency] is the
frequency at which the inverter starts to output DC
voltage during deceleration.
FU1-09 [DC Injection Braking On-delay Time] is the
inverter output blocking time before DC injection braking.
FU1-10 [DC Injection Braking Voltage] is the DC voltage
applied to the motor and is based on FU2-33 [Rated
Current of Motor].
FU1-11 [DC Injection Braking Time] is the time the DC
current is applied to the motor.
[DC Injection Braking Operation]
Output Frequency
Time
FX-CM
ON
Output Voltage
Time
Time
Stop Command
Output Cutoff
Output Cutoff
FU1
DcBr freq
08 5.00 Hz
5.00
08
Factory Default: 5.00 Hz 5.00
FU1
DcBlk time
09 0.10 sec
0.10
09
Factory Default: 0.10 sec 0.10
FU1
DcBr value
10 50 %
50
10
Factory Default: 50 % 50
FU1
DcBr time
11 1.0 sec
1.0
11
Factory Default: 1.0 sec 1.0
Output Frequency
Time
FX-CM
ON
Output Voltage
Time
Time
Stop Command
FU1
-
08
[DCBr Freq]
FU1
-
10
[DCBr Value]
t1
t2
t1: FU1-09
t2: FU1
-
11