(3)
Compared output
(a) High Speed counter module has a compared output function used to compare present count
value with compared value in size to output as compared.
(b) Available compared outputs are 2 for 1 channel, which can be used separately.
(c) Compared output conditions are 7 associated with >, =, < .
(d) Parameter setting
Compared output mode setting
Upper setting value is saved in special K area.
Compared output condition Memory address (word) Value
*2)
Present Value < Compared Value
Channel 0 : K302
Channel 1 : K330
Channel 2 : K358
Channel 3 : K386
Set to “0”
Present Value ≤ Compared Value Set to “1”
Present Value = Compared Value Set to “2”
Present Value ≥ Compared Value Set to “3”
Present Value > Compared Value Set to “4”
Compared value 1 ≤ Count value ≤ Compared value 2 Set to “5”
Count value Compared value 1,
Count value Compared value 2
Set to “6”
*2) If compared output value not set to 0~6 using counter, error code 23 will be occurred.
In order to make actual comparison enabled after compared output condition set, the
compared enable signal is to be On.
Classification
Area per channel
Operation
Ch. 0 Ch. 1 Ch. 2 Ch. 3
Count enable signal K2600 K2700 K2800 K2900 0: N/A, 1: enable
Compared enable signal K2604 K2704 K2804 K2904 0: forbidden, 1: enable