(3)
Compared output
(a) High Speed counter module has a compared output function used to compare present count
value with compared value in size to output as compared.
(b) Available compared outputs are 2 for 1 channel, which can be used separately.
(c) Compared output conditions are 7 associated with >, =, < .
(d) Parameter setting
■ Comp. output mode setting
■ Upper setting value is saved in special K area.
Compared output condition
Memory address (word)
Value
*2)
Comp output 0 Comp output 1
Present Value < Compared Value
Ch.0 K302
Ch.1 K332
Ch.2 K362
Ch.3 K392
Ch.4 K2222
Ch.5 K2252
Ch.6 K2282
Ch.7 K2312
Ch.0 K303
Ch.1 K333
Ch.2 K363
Ch.3 K393
Ch.4 K2223
Ch.5 K2253
Ch.6 K2283
Ch.7 K2313
Set to “0”
Present Value ≤ Compared Value Set to “1”
Present Value = Compared Value Set to “2”
Present Value ≥ Compared Value Set to “3”
Present Value > Compared Value Set to “4”
Compared value 1 ≤ Count value ≤ Compared value 2 Set to “5”
Count value ≤ Compared value 1,
Count value ≥ Compared value 2
Set to “6”
*2)
If compared output mode set value is other than 0~6 at using counter, error code ‘23’ occurs.