Power Up: DLP-504 363-205-401
Page 4 of 6 Issue 7, March 1997
12.
!
DANGER:
A high discharge current is present at connector head if TESTING
indicator is lighted. Batteries must not be connected or disconnected
when TESTING indicator is lighted.
NOTE:
This test must run for a full 15 minutes to be valid or until all batteries
indicate
REPLACE
. The
STOP
button should only be used if a problem
occurs during the test, if the test is to be terminated early because of loss
of AC power, or if all batteries indicate
REPLACE
. The
START/CONTINUE
button is used to continue the test if no problem is
found.
Depress
197A
test set
START/CONTINUE
button.
Response: At
197A
test set,
TESTING
indicator is lighted,
READY
indi-
cator is off, and
TIME
display is counting time.
13.
NOTE:
If one, two, or three, but not all, batteries show
REPLACE
during the test
period, the remaining batteries still must be tested for the full 15 minutes.
Does test set show
REPLACE
for all batteries within the 15-minute test period
shown on
TIME
display?
If
YES,
then continue with Step
14.
If
NO,
then proceed to Step
15.
14.
!
DANGER:
A high discharge current is present at connector head if TESTING
indicator is lighted. Batteries must not be connected or disconnected
when TESTING indicator is lighted.
Depress test set
STOP
button.
Response:
STOP
indicator on test set lights
Proceed to Step
17.