363-205-401 Power Up: DLP-533
Issue 7, March 1997 Page 3 of 6
10. Does test set fan operate?
If
YES,
then proceed to Step
15.
If
NO,
then proceed to Step
35.
11. On test set connector head, remove battery lead and check for blown fuse(s).
12. Is fuse(s) blown?
If
YES,
then continue with Step
13.
If
NO,
then proceed to Step
14.
13. Replace fuse(s) and repeat from Step
5.
14.
NOTE:
Test set may be used for testing using one, two, three or all four
BATT
plug positions.
Defective test set or connector head. Note defective
BATT
plug position(s).
Continue with test procedures using remaining
BATT
plugs.
15. Does test set
TIME
display indicate
00 MIN:00 SEC
without blinking?
If
YES,
then continue with Step
16.
If
NO,
then proceed to Step
35.
16. Does status display indicate which battery was connected, status (
GOOD
or
REPLACE
) of the battery, and is
READY
indicator lighted?
If
YES,
then continue with Step
17.
If
NO,
then proceed to Step
35.
17. Does status display indicate
GOOD
or
REPLACE
?
If
YES,
then proceed to Step
19.
If
NO,
then continue with Step
18.