Power Up: NTP-008 363-205-401
Page 2 of 4 Issue 7, March 1997
DO ITEMS BELOW IN ORDER LISTED FOR DETAILS, GO TO
2. Get support apparatus listed:
J99409OB, L1 optical backplane maintenance kit
•Box of
Kimwipes
*
wipers (Lint Guard Poly Shield, Stock No.
34155), or equivalent
Bottle of isopropyl reagent alcohol with dispenser
Can of compressed air
DMM (digital multimeter) with an accuracy of 1.0% and an
ac/dc input impedance of 1 megohm.
*. Registered trademark of Kimberly-clark Corp.
3.
!
CAUTION:
An electrostatic discharge wrist strap with a minimum
resistance of 250K Ohms should be worn when handling
Series 5 circuit packs to prevent possible damage to the
circuit packs. Before using the wrist strap, check it for
opens, shorts, and minimum resistance value. If the strap
does not pass these checks it should not be used. To avoid
possible personal injury while using the wrist strap, do not
connect it to the power shelf or adjacent portions of the RT
frame. Connect the wrist strap to ESD GRD jack on the fan
unit, if present. If grounding jack is not present, connect
wrist strap to bare-metal section of the frame well away from
the power shelf.