4-4
CDA3000 Operation Manual
4  Commissioning
4.2.2 Serial commis-
sioning with  
D
RIVEMANAGER 
Prerequisite:
• All inverter modules are fully connected.
• The first drive is already fully commissioned.
• A PC with installed D
RIVEMANAGER user software (V2.3 or higher) is 
connected.
  
For additional information refer to the DRIVEMANAGER HELP.
Step Action Comments
1
Connect your PC to the inverter 
module of the first drive and switch 
on the power to the inverter.
Use a standard serial cable (9-pin 
D-SUB, pin-and-socket) e.g. LUST 
accessory CCD-SUB90x .
2
START DriveManager.
Automatically connects to the linked 
inverter module.
If the connection fails, check the settings in the Tools > Options menu and 
try again by clicking on the icon .
3
Save the current data set by clicking 
on the icon  , 
either in  the parameter database 
(directory: c:/../userdata) of the 
D
RIVEMANAGER or to a floppy disk 
(a:/).
Clicking on the icon always saves the 
current data set of the connected 
device.
Assign the file a name of your choice.
4
Connect your PC to the inverter module of the next drive and switch on the 
power to the inverter.
5
Click on the icon   to connect 
between the D
RIVEMANAGER and the 
now connected device. 
6
Click on the icon   to  load the 
data set saved in step 4 into the 
device.
The data set is filed  in the device as 
user data set 1.
7
Back-up the setting in subject area 
_15FC with parameter 150 -SAVE
Repeat steps 4 ... 7 on each additional drive.
Saving a data set from the 
device to a file
Loading a data set from a file 
into the device
Remember to
save the set-
ting.
• Call up subject area 
_15FC
• Select parameter 
150-SAVE
• Set parameter to 
START and confirm