CDA3000 Operation Manual
4-13
4 Commissioning
1
2
3
4
5
A
DE
EN
FR
IT
ES
FR
4.5 Field-Oriented
Regulation (FOR)
Apply this mode of commissioning when you want to run a motor with
encoder feedback - control mode Field Oriented Regulation (FOR).
FOR commissioning, traction
and lifting drive with encoder
Unregulated test run
Prerequisite:
Inverter module fully connected.
Control terminals wired according to
terminal assignment 3,
see page 3-15 .
•A K
EYPAD KP200 or a PC with DRIVEMANAGER (version V2.3 or
higher) is connected. For operation see section 4.6 and 4.7.
Attention: Make sure the rotating drive in your machine cannot cause
any damage (e.g. overrunning its stop limit) during commis-
sioning.
Step Action Comment
1
Switch on the power to the
inverter module.
After power-up the inverter module per-
forms a self-test (lasting approx. 1... 3 s).
2
Check that your drive can be run
at the rotating field frequency and
with the ramps as per the factory
setting.
Quick jog = 50 Hz
Acceleration ramp = 20 Hz/s
1)
Deceleration and stop ramp = 20 Hz/s
1)
If this is not possible, change the
parameters below. Back-up the
setting in subject area _15FC with
parameter 150 -SAVE
Subject area/Parameter
Quick jog _30OL 303-FMAX1
Acceleration
ramp _59DP 590 -ACCR1
Deceleration
ramp _59DP 592 -DECR1
Stop ramp _59DP 594-STPR1
3
In subject area _15FC set param-
eters
152-ASTER to DRV_4.
DRV_4 = Control terminal assignment
Quick jog driving profile +
encoder
4
Close ENPO contact. ENPO active enables power stage.
5
Start drive by closing the STL or
STR contact.
STL = Start counter-clockwise
STR = Start clockwise
6
Check direction of rotation of
drive.
With STR active, motor rotates clockwise
(2)
(1) Direction of view.
6
Brake drive by opening the start
contact.
Drive brakes down to a standstill.
7
Open ENPO contact.
ENPO inactive safely disables power
stage.
1) Factory setting from BG1
to BG5 (15 kW ) = 20 Hz/s, as
from BG6 (22 kW) to
BG8 = 5 Hz/s
Remember to
save the set-
ting.
Call up subject area
_15FC
Select parameter
150-SAVE
Set parameter to
START and confirm
(2)
(1)