2
220-240V/CE Control Interface
Important Installation Information
Install in accordance with all national and local electrical codes.
Check for short circuited loads during new installations before wiring the GRX-TVI.
Caution: Multiple feeds may enter this enclosure. Locate and lock each feed circuit breaker/MCB in the OFF position
before wiring the Interface.
Proper short circuit and overload protection must be provided at the distribution panel. You can use up to a 20A (16A for CE)
maximum circuit breaker/MCB or equivalent (tripping curve C according to IEC 898/EN60898 is recommended) with adequate
short circuit breaking capacity for your installation.
Terminal blocks are rated for two #12-22 AWG (0.5-2.5 mm
2
) wires per terminal.
Strip 3/8 in. (10 mm) of insulation from wires.
Wiring Diagram A shows a GRX-TVI wired from one distribution panel. If the
power requirement of the complete system is less than an MCB/circuit
breaker rating, one feed can be jumpered inside the enclosure (as shown).
Wiring Diagram B shows a GRX-TVI wired from two separate distribution panels that may be different phases or voltages.
Use the internal terminal block label to see where to land wires.
The label shows two separate Hot/Live terminals (L
1/H1 & L2/H2).
L
1/H1 is the Hot/Live feed to power the lighting load.
L
2/H2 is the Hot/Live feed that powers internal circuitry of the GRX-
TVI.
L2/H2 has a 100-127V connection and a 220-240V connection - use
only the one corresponding to line voltage for your application.
Note 1: Not all terminal blocks receive a connection.
Note 2: The power feed to the Control Unit and L2/H2 of the GRX-
TVI must be the same phase!
Class 2/PELV, 0-10V wiring from a ballast to the GRX-TVI-
CE must be separated from the power wiring. Enter the
Class 2/PELV wires through the knockout adjacent to the 0-10V terminal blocks. The Nomex
®
barrier ensures
separation and is flexible to allow access to the terminals. The barrier must be in place when installation is
complete.
GRX-TVI Internal Terminal Block Label Definitions
Use only one input according to Input Voltage:
L
2/H2 240V Power input for GRX-TVI control (line/mains voltage must be 220-240V)
L
2/H2 127V Power input for GRX-TVI control (line/mains voltage must be 100-127V)
N2 Neutral for GRX-TVI control
DL
2/DH GRAFIK Eye 3000 Series Control Unit Lighting Zone connection (Phase Control Input to GRX-TVI)
L
1/H1 Power input for lighting load
N
1 Neutral for lighting load (2 terminals provided and internally tied together one for input neutral and one
for load neutral)
SL
1/SH1 Switched output to power lighting load
+ - 0-10V control signal wires (
ballast must provide a 0-10V source only)
10mm
(3/8in.)
L2/H2 100-127V
N2
DL2/DH2
L1/H1 100-277V
N1
N1
SL1/SH1
0-10 Volt
L
2
/H
2
220-240V/CE
Use only if
your
line/mains
voltage is
220-240V.
Use only if your line/mains voltage is
120-127V.
Input from distribution
panel.