S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373b 5 06.21.12
Wiring
RS232 Link
•Standard9-pinserialconnectorplugsintoRS232
equipment,andtoQSE-CI-NWK-E.
•Mustbe50ft(15m)orless.
RS232 Signals
Signals Pin on 9-Pin Cable
Com 5
TxD 3
RxD 2
1 2 3 4
1 2
A B C
1 2 3 4 5 6 L N
4 3 2 1
To additional QS devices
RS232 Cable
50ft(15m)
max.
EthernetLink:CAT5Cable:328ft(100m)max.
COM
TxD
RxD
RS232 Link
ToPCorAV
Equipment
RearViewofGRAFIKEye®QSControlUnit
Toexternalpowersupply
QSLink:
1:Common
2:Power
3:MUX
4:MUX
Seenextpage.
Do not connect Pin 2 if using
externalpowersupply.
QS Link
Ethernet Link Wiring
•StandardCAT5cableconnectsQSE-CI-NWK-E
Interface to PC, router, or other Ethernet source.
•Nocrossovercableneeded.
•Mustbe328ft(100m)orless.
•Ethernetnetworkandcableprovidedbyothers.