S P E C I F I C AT I O N S U B M I T TA L Page
Job Name:
Job Number:
Model Numbers:
QS System QSE-CI-NWK-E Control Interface
369373b 6 06.21.12
Wiring (continued): QS Link Wiring Methods (choose one)
Powered by GRAFIK Eye® QS Control Unit
Powered by a QS Link Power Supply
1 2 3 4
1 2
A B C
1 2 3 4 5 6 L N
4 3 2 1
Toadditionalwallstations/
control interfaces
Toadditionalwallstations/
control interfaces
RearViewofGRAFIKEye
® QS
ControlUnit
RearViewof
GRAFIKEye
® QS
ControlUnit
QS
Link
QS
Link
QS Link
1:Common
2:Power
3:MUX
4:MUX
DataLink:
4:MUX
3:MUX
See QS Link
WireSizestable
IECPELV/NEC®Class2Powerwiring:
2:Power
1:Common
SeeQSLinkWireSizestable
•SystemcommunicationusesIECPELV/NEC® Class 2
wiring.
•Followalllocalandnationalelectricalcodeswhen
installingIECPELV/NEC
®Class2wiringwithline
voltage/mainswiring.
•Eachterminalacceptsuptotwo18AWG(1.0mm²)
wires.
•Totallengthofcontrollinkmustnotexceed2000ft
(610m).
•TypicalWireSizes:SeeQSLinkWireSizestable.
•Connecttheterminal1,3,and4connectionstoall
controlunits,wallstations,andcontrolinterfacesinthe
QSsystem.Forterminal2connectivity,seebelow.
4 3 2 1
Lutron Cable
SeeQSLinkWireSizestable
QSPS-P1-1-50
(providesupto8
powerdrawunits)
Topowersource
(1)18AWG
(1.0mm
2
)
Common
(1)twistedpair
22AWG
(0.5mm
2
)
QS Link Wire Sizes (check compatibility in your area)
QS Link Wiring Length Wire Gauge Lutron Cable Part Number
<500ft(153m)
Power(terminals1and2)
1pair18AWG(1.0mm
2
)
GRX-CBL-346S(non-plenum)
GRX-PCBL-346S(plenum)
Data(terminals3and4)
1twisted,shieldedpair22AWG(0.5mm
2
)
500–2000ft
(153–610m)
Power(terminals1and2)
1pair12AWG(4.0mm
2
)
GRX-CBL-46L
(non-plenum)
GRX-PCBL-46L(plenum)
Data(terminals3and4)
1twisted,shieldedpair22AWG(0.5mm
2
)
Do not use
external
powersupply
if connecting
Pin 2
Donotuseexternalpower
supply if connecting Pin 2