Intrinsically Safe ERBX Batch Controller with 1 x transistor output Type (Hx)
For Programming, press PROG/ENTER button for 7 seconds.
Press STOP button to access functions and Press START button to reach sub-functions
Setting up a value in sub function, press PROG and get use of buttons START & STOP to adjust a value
Once the desired value is adjusted, press PROG button to finalize it
Once all sub functions are set, press PROG button for 3 seconds to go back to operational mode
SETUP FUNCTIONS AND VARIABLES
1
TOTAL
11 UNIT L - m³- kg - lb - GAL - USGAL - bbl - no unit
12 DECIMALS 0 - 1 - 2 - 3 (Ref: displayed value)
13 K-FACTOR 0.000010 – 9,999,999 (As per Flowmeter report)
14 DECIMALS K-FACTOR 0 – 6 (This seng depend upon seng 24)
15 BATCH MAXIMUM X,XXX,XXX Quanty
2 FLOW RATE
21 OVERRUN Disable - Enable
22 TIME 0.1 - 999.9 seconds
3 DISPLAY
31 FUNCTION Total - Flowrate
32 BACKLIGHT (OPTIONAL) O - Green - Amber
33 BL. BRIGHTNESS 1 – 5
4 POWER MANAGEMENT
41 LCD UPDATE Fast - 1 sec - 3 sec - 15 sec - 30 sec - o
42 BATTERY MODE Operaonal – Shelf
5 FLOWMETER
51 SIGNAL REED_LP
6 OTHERS
61 TYPE / MODEL F030 (Don’t touch)
62 SOFTWARE VERSION MCN0121 (Don’t touch)
63 SERIAL NO. 12345 (Don’t Touch)
64 PASS CODE 0000 – 9999 (Change If required)
65 TAG NUMBER 0000000 – 9999999 (Don’t touch)