13 Configuration and Operation MacroAir AirLynk
© 2019 MacroAir Technologies Toll Free: 866 668-3247 Fax: 909 890-2313 www.macroairfans.com
Rev Date: 071519
A Quick Start Guide, cont.
BACnet MSTP setup
1. Us the up and down arrows on the right to navigate to “Main Page 2”
from “Main Page 1” by selecting
2. Select “MSTP Setup” on “Main Page 2”
3. From “MSTP Settings” you can set the various settings needed to operate the fans
through BACnet MSTP
Proto- Protocol (BACn for BACnet MSTP)
Baud- Baudrate of the protocol
Addr- Address of the PLC
Data- Data bit number
Pari- Parity (Nul-None, Odd, Eve-Even)
Stop- Stop bit
BACnet IP setup
1. Us the up and down arrows on the right to navigate to “Main Page 2” from “Main Page
1” by selecting
2. Select “IP Setup” on “Main Page 2”
3. From “IP Settings” you can set the various settings needed to operate the fans through
BACnet IP
IP- IP address
Net MSK- Net Mask
Port- BACnet/IP port (0= port 37808)
DHCP- Enabled/Disable DHCP
Gate- Default Gateway
DNS1/2- DNS server