7 Network Installation MacroAir AirLynk
© 2019 MacroAir Technologies Toll Free: 866 668-3247 Fax: 909 890-2313 www.macroairfans.com
Rev Date: 071519
Network Wiring Requirements
Use Stranded Twisted Pair, CAT5e (or higher grade) shielded cable
Minimum 24 AWG (0.5mm) cross section
Route wires as far away as possible from high voltage AC cables, fluorescent lights, arc
welders, and other equipment that transmits EMI (electromagnetic interference).
For 370 Fans:
Ground the shielding and drain wire at only one point of the cable run
Add Repeaters/Isolators (1/5fans)
Daisy Chain
Networked MacroAir fans must be connected in one single line, referred to in this document as a
“daisy chain”. The characteristics of a proper daisy chain are: one beginning (AirLynk) and one
end (last fan).
If the fans are not connected in one line/chain there will be a de-graduation of the
communication signal and the network may not function as intended (fans in the network may
not operate).
¤
- Control Panel
VFD MC