Majestic • MDVI30IN, MDVI35IN, MDVI30IL, MDVI35IL Owner’s Manual • 2205-981 Rev. G • 7/18
Intellire™ Plus Ignition System - (continued)
Symptom Possible Cause Corrective Action
4. Pilot lights but contin-
ues to spark, and main
burner will not ignite.
(If the pilot continues
to spark after the
pilot ame has been lit,
ame rectication has
not occurred.)
A. A shorted or loose connection in ame
sensing rod.
Verify all connections to wiring diagram in manual. Verify
connections underneath pilot assembly are tight. Verify
ame sense or igniter wires are not grounding out to metal
chassis, pilot burner, pilot enclosure or screen if present, or
any other metal object.
B. Poor ame rectication or contaminated
ame sensing rod.
With xed glass assembly in place, verify that ame is en-
gulng ame sensing rod on left side of pilot hood. Flame
sensing rod should glow shortly after ignition. With a multi-
meter, verify that current in series between module and
sense lead is at least 0.14 microamps. Verify correct pilot
orice is installed and gas inlet is set to pressure speci-
cations. Polish ame sensing rod with ne steel wool to
remove any contaminants that may have accumulated on
ame sensing rod.
C. Module is not grounded. Verify module is securely grounded to metal chassis of ap-
pliance. Verify that wire harness is rmly connected to the
module.
D. Damaged pilot assembly or contami-
nated ame sensing rod.
Verify that ceramic insulator around the ame sensing rod
is not cracked, damaged, or loose. Verify connection from
ame sensing rod to white sensor wire. Polish ame sens-
ing rod with ne steel wool to remove any contaminants
that may have accumulated on ame sensing rod. Verify
continuity with a multi-meter with ohms set at lowest range.
Replace pilot if any damage is detected.
5. Appliance lights and
runs for a few minutes
and then shuts down
and/or appliance cycles
on and off.
A. A shorted or loose connection in ame
sensing rod.
Verify all connections to wiring diagram in manual. Verify
connections underneath pilot assembly are tight. Verify
ame sense or igniter wires are not grounding out to metal
chassis, pilot burner, pilot enclosure or screen if present, or
any other metal object.
B. Poor ame rectication or contaminated
ame sensing rod.
With xed glass assembly in place, verify that ame is en-
gulng ame sensing rod on left side of pilot hood. Flame
sensing rod should glow shortly after ignition. With a multi-
meter, verify that current in series between module and
sense lead is at least 0.14 microamps. Verify correct pilot
orice is installed and gas inlet is set to pressure speci-
cations. Polish ame sensing rod with ne steel wool to
remove any contaminants that may have accumulated on
ame sensing rod.
C. Logs are set up incorrectly. Remove and reinstall logs per the log placement
instructions.
D. Damaged pilot assembly or contami-
nated ame sensing rod.
Verify that ceramic insulator around the ame sensing rod
is not cracked, damaged, or loose. Verify connection from
ame sensing rod to white sensor wire. Polish ame sens-
ing rod with ne steel wool to remove any contaminants
that may have accumulated on ame sensing rod. Verify
continuity with a multi-meter with ohms set at lowest range.
Replace pilot if any damage is detected.