Thermostat Settings
Bin Thermostat:
The bin thermostat sensing bulb is located in the ice
chute on modular models and in the bin thermostat
holder on the right side of the bin on self storage models.
The bin thermostat turns the ice machine on and off as
the level of ice in the bin changes. Use the indicator on
the ice machine label as the initial setting and adjust as
required.
Evaporator Low Temperature Safety Thermostat:
The evaporator low temperature safety thermostat
protects the ice machine if the evaporator temperature is
too cold. Refer to chart for correct setting.
1
2
3
4
5
6
7
1
2
3
4
5
6
7
Bin Thermostat
Small Numbers = Less ice in bin
Large Numbers = More ice in bin
Start at Chart Setting, then adjust
as required
Evaporator Low Temperature
Safety Thermostat
Refer to chart for setting
Incorrect settings will cause ice
machine to shut off prematurely