146 Part Number 000014797 Rev02 05/18
Suction Temperature Low Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist” on
page 136
Discharge Pressure
Discharge temperature is too low, and is affecting
suction temperature, refer to “Freeze Cycle Discharge
Temperature Low Checklist” on page 143.
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-Manitowoc components in system
Improper water supply over evaporator refer to
”Water System Checklist” on page 137.
Loss of heat transfer from tubing on back side of
evaporator
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of
refrigeration system
TXV starving
NOTE: Do not limit your diagnosis to only the items listed
in the checklists.