Questions and Answers

  • S
    Steven BarnesAug 8, 2025
    Why is the Maruson UPS beeping twice every second?
    • R
      Ricardo WadeAug 8, 2025
      The Maruson UPS is beeping twice every second because it is overloaded. To resolve this, remove some of the devices connected to the UPS. If the UPS is locked in Bypass mode after repetitive overloads, first remove some of the devices connected to the UPS, then shut down the UPS and restart it.
  • J
    James RiversAug 12, 2025
    What to do if fault code 43 is shown on Maruson UPS?
    • C
      cathymejiaAug 12, 2025
      If fault code 43 is displayed on your Maruson UPS, it means the UPS shut down automatically due to an overload at the output. Remove some of the devices connected to the UPS and restart it.
  • J
    Jon LopezAug 16, 2025
    What to do if fault code 14 is shown on Maruson ULT-W1K?
    • J
      Jessica AlexanderAug 16, 2025
      If fault code 14 is displayed on your Maruson UPS, it indicates that the UPS shut down automatically because a short circuit occurred at the UPS output. Check the output wiring and the devices connected to the UPS to see if any are causing a short circuit.
  • M
    Matthew OlsenAug 20, 2025
    Why is battery backup time shorter than nominal value in Maruson ULT-W1K UPS?
    • D
      David MartinezAug 21, 2025
      The battery backup time might be shorter than expected for two reasons: the batteries may not be fully charged or the batteries are defective. Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
  • R
    Robert FlowersAug 25, 2025
    What to do if Maruson UPS shows fault codes 01, 02, 03, 04, 11, 12, 13, 41 and 45?
    • J
      Julie FordAug 26, 2025
      If your Maruson UPS displays fault codes 01, 02, 03, 04, 11, 12, 13, 41 and 45, it indicates an internal fault. Contact your dealer.
  • J
    jeffrey83Aug 29, 2025
    How to fix Maruson ULT-W1K when LCD is flashing and alarm is sounding?
    • N
      Nancy RogersAug 29, 2025
      If the icon is flashing on the LCD display and the alarm is sounding every second, it means the external or internal battery is incorrectly connected. Check if all batteries are connected well.
  • J
    jamie16Sep 3, 2025
    How to troubleshoot Maruson UPS with no indication and alarm?
    • S
      Samantha StewartSep 3, 2025
      If your Maruson UPS has no display or alarm, even when the mains power is normal, it could be due to these reasons: The AC input power is not connected well. Check if the input power cord is firmly connected to the mains. Alternatively, the AC input may be connected to the UPS output. Ensure you plug the AC input power cord into the AC input correctly.

Maruson ULT-W1K Specifications

General IconGeneral
CategoryUPS
ModelULT-W1K
VA Rating1000VA
Wattage600W
Outlets8