Crossfire LCD - Installation and Programming Manual
14
Version 1.5 | Revision B | May 2012
MENU 1-7 Fault Relay
The Menu “Fault Relay” lets you define which zones of the system that
act the Fault Relay.
By accessing this menu, you can select zones that will trigger the relay.
As the cursor keys to select “Up” and “Down” appears on the display messages
Trigger” or “Not Trigger”.
MENU 2 - TIME
MENU 2 -1 Pre-Alarm Time
The Menu “Pre-Alarm Time allows you to set the timing of pre alarm to
be, whenever the Control Panel is placed in “Day Mode”.
On alarm, the contro panel will only only signal locally by the buzzer, and
ended the pre-alarm time set, if there was no further action, will trigger outputs Sounder and/or Alarm
relay.
To enter the menu you should press “Ent / Esc”.
This time is configurable from 0 seconds to 10 minutes, using the cursor keys “Up” and “Down”
MENU 2 -2 Sounder 1
The Menu “Sounder 1” lets you set the timer of ringing sirens connected to
the Sounder 1 output signal .
To enter the menu you should press “Ent / Esc”.
This time is configurable from 0 seconds to 10 minutes, using the cursor keys “Up” and “Down”.
MENU 2 -3 Sounder 2
O The Menu “Sounder 1” lets you set the timer of ringing sirens connected
to the Sounder 2 output signal .
To enter the menu you should press “Ent / Esc”.
This time is configurable from 0 seconds to 10 minutes, using the cursor keys “Up” and “Down”.
MENU 3 - TEST MODE
This menu lets you put your Control Panel in test mode. The Test mode
allows rehearse the zones of Control Panel without alarms that are
generated by the outputs or the siren or by activation of the alarm relay.
By entering this menu, you can select which zones you want to put in test mode.
If some zone remain active in test mode, the LEDTest” illuminates.
On completion of a test that simulates alarm or fault, will be shown in the display the correspondent
event, until pressed one of the cursor keys to return to the Test Menu.
Note: The output of the Test mode removes all alarm and fault indications and momentarily removes
the supply of zones.
MENU 4 - PROGRAM CODE
This menu allows you to reprogram the Technical Code Level 3 for access
to the system.
To select a new sequence number, you should use the cursor keys “Up” and
“Down” to select the value, and keys “Left and” Right “to select the position of the value.
Menu 1-7 Fault
Relay
<-
Menu 2-2
Sounder 1
<->
Menu 2-3
Sounder 2
<-