Switching  on the air conditioner
         The current leakage switch 
jumps to turn off 
         Junction wire looses and collides with  the outer 
cover. 
         Degraded  capability of wire insulation.
         Insulation capability of 
some components  has 
lowered.
Check the resistance 
of every component  
by multimeter
   Water comes into the plug or electric components. 
The fuse is blown 
or air limit switch 
jumps to turn off 
Is the voltage 
of power supply lower 
than 15% of rated voltage
(220V)?
         Yes
         The voltage is low, 
please add manostat. 
         Short circuit 
somewhere.
         Partially  short circuit in 
some components.
         Fuse capacity 
is adequate or not?
         Yes
         No
         No
         Replace with adequate 
fuse.
         Check as the above
-mentioned method.
Short circuit in the 
electric wire or 
connection wire.
         Without  any 
response
         Check whether 
the receptacle has 
power or not.
Power supply error
         Strong circuit breaks 
the circulation.
The transformer faults.
The main control board 
faults.
FAULT DIAGNOSIS BY SYMPTOM
16