OM AGSD-1 69
SET UNIT SPs (9)
Ice Time Delay=XXhrs
Clear Ice Timer=No
PVM = Multi Point
Phase Voltage Monitor (PVM) can be single or multi-point and applies to units with wye-
delta starters. Select NONE (SSS) for units with solid-state starters, which have an internal
PVM capability. If NONE (SSS) is not selected for solid-state starter units, the unit will not
operate.
SET UNIT SPs (10)
Remote Evap=No
SET UNIT SPs (11)
Sensor Offset
Evap LWT= X.XF
Evap EWT= X.XF
SET UNIT SPs (12)
Sensor Offset
OAT= XX.XF
SET UNIT SPs (13)
CLOCK
mm/dd/yyyy
hh:mm day
SET UNIT SPs (14)
Units = F/psi
Lang = ENGLISH
SET UNIT SPs (15)
Protocol=
Ident Number=
Baud Rate=
SET UNIT SPs (16)
Enter Password:0000
Active Password
Level:none