IOMM AGZ-5 AGZ 026B through 130B 45
Table 31, AGZ 026BB/BH - 070BB/BH, Electrical Data, Multi-Point
(106°F to 125°F)
Electrical Circuit #1 Electrical Circuit #2
Power Supply Power Supply
Field Wire Field Wire
AGZ
Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max. Fuse
or HACR
Breaker
Size
Minimum
Circuit
Ampacity
(MCA)
Qty
Wire
Gauge
75C
Recomm’d
Fuse
or HACR
Breaker
Size
Max.
Fuse
or HACR
Breaker
Size
230 70 3 #4 80 90
70
3
#4 80 90
380 42 3 #8 50 50
40
3
#8 50 50
460 36 3 #8 45 45
36
3
#8 45 45
026B
575 27 3 #10 35 35
27
3
#10 35 35
230 70 3 #4 80 90
81
3
#4 100 110
380 42 3 #8 50 50
50
3
#8 60 60
460 36 3 #8 45 45
42
3
#8 50 50
030B
575 27 3 #10 35 35
34
3
#10 45 45
230 81 3 #4 100 110
81
3
#4 100 110
380 50 3 #8 60 60
50
3
#8 60 60
460 42 3 #8 50 50
42
3
#8 50 50
035B
575 34 3 #10 45 45
34
3
#10 45 45
230 88 3 #3 110 110
88
3
#3 110 110
380 60 3 #6 70 80
60
3
#6 70 80
460 44 3 #8 50 60
44
3
#8 50 60
040B
575 37 3 #8 45 50
37
3
#8 45 50
230 88 3 #3 110 110
109
3
#2 125 150
380 60 3 #6 70 80
70
3
#4 80 90
460 44 3 #8 50 60
55
3
#6 70 70
045B
575 37 3 #8 45 50
45
3
#8 60 60
230 109 3 #2 125 150
109
3
#2 125 150
380 70 3 #4 80 90
70
3
#4 80 90
460 55 3 #6 70 70
55
3
#6 70 70
050B
575 45 3 #8 60 60
45
3
#8 60 60
230 109 3 #2 125 150
130
3
#1 175 175
380 70 3 #4 80 90
84
3
#4 100 110
460 55 3 #6 70 70
65
3
#4 80 90
055B
575 45 3 #8 60 60
55
3
#6 70 70
230 130 3 #1 175 175
130
3
#1 175 175
380 84 3 #4 100 110
84
3
#4 100 110
460 65 3 #4 80 90
65
3
#4 80 90
060B
575 55 3 #6 70 70
55
3
#6 70 70
230 134 3 1/0 175 175
161
3
2/0 200 225
380 82 3 #4 100 110
91
3
#3 110 125
460 67 3 #6 80 90
80
3
#4 100 110
070B
575 55 3 #6 70 70
65
3
#6 90 90
NOTES:
1. All Electrical Data notes are on page 49.
2. Conduit hubs are not supplied.