46 AGZ 026B through 130B IOMM AGZ-5
Table 32, AGZ 075BB/BH – 130BB/BH, Electrical Data, Single Point
(Above 105°F)
Power Supply Max. Fuse
Field Wire
AGZ Unit
Size
Volts
Minimum
Circuit
Ampacity
(MCA)
Quantity
Wire
Gauge
75C
Recomm’d.
Fuse
Or HACR
Breaker
Size
Or HACR
Breaker
Size
230 362 6 4/0 400 400
380 194 3 3/0 225 225
460 187 3 3/0 225 225
075B
575 145 3 1/0 175 175
230 382 6 250 450 450
380 234 3 250 250 250
460 200 3 4/0 225 225
085B
575 151 3 1/0 175 175
230 401 6 350 450 450
380 270 3 300 300 300
460 211 3 4/0 250 250
090B
575 157 3 2/0 175 175
230 462 6 350 500 500
380 273 3 300 300 300
460 230 3 4/0 250 250
100B
575 187 3 3/0 200 200
-
230 526 6 - (2) 300 600 600
380 307 3 350 350 350
460 263 3 300 300 300
110B
575 211 3 4/0 225 225
-
230 571 6 - (2) 350 600 600
380 352 6 - (2) 4/0 400 400
460 286 3 350 300 300
120B
575 219 3 4/0 250 250
-
230 613 6 - (2) 350 700 700
380 393 6 250 450 450
460 307 3 350 350 350
130B
575 228 3 250 250 250
NOTES:
1. Units operating in ambient temperatures of 95°F (35°C) and above must use the Maximum
Fuse or HACR Breaker size.
2. All Electrical Data notes are on page 49.
3. (2) in column with wire qty. indicates that two conduits are required.
4. Conduit hubs are not supplied.